Intertek Directory of Building Products

Coopers Fire Ltd. 20 Minute to 3 Hour Fire Rated FireMaster Concertina Fire Barrier Company: Coopers Fire Ltd.

Product Covered:
Coopers FireMaster Concertina Fire Curtain

AIR LEAKAGE RATINGS
The following ratings pertain to the FireMaster Concertina Fire Curtain using either the EFP A1 or EFP 4/1000 curtain fabrics.
Test Standard Test Type Ratinga
UL 1784 Ambient & Elevated Temperatures ≤ 3.0 cfm/ft2 at 0.10 in. of w.c.
aThis assembly was evaluated both with and without an artificial bottom seal. See minimum sizes below pertaining to each classification. When complying with the minimum assembly size for evaluation without artificial bottom seal, the assembly may be installed in areas where pressurization is provided to control smoke movement in accordance with Section 4.3.2 of NFPA 105 (2019).

FIRE RATINGS
The following ratings pertain to the FireMaster Concertina Fire Curtain with EFP 4/1000 curtain fabric when installed in steel stud/gypsum or masonry wall applications.
Test Standard Rating
UL 10D 180 minute
UL 10B, UL 10C, NFPA 252a 20 minute without hose streama
aThe UL 10B, UL 10C, and NFPA 252 standards apply only to 20 minute fire endurance ratings without hose stream.  Acceptance of the UL 10B, UL10C, and NFPA 252 ratings for the fire curtain product is ultimately at the discretion of the Authority Having Jurisdiction.

MINIMUM SIZE LIMITATIONS (SMOKE-RATED ASSEMBLIES)
System Type Minimum
Curtain Height
Minimum Total
Plan Lengtha, b
Closed (Without Side Guides)
With or Without Artificial Bottom Seal
8'-0" None
Open (With Side Guides)
Evaluated With Artificial Bottom Seal
8'-0" 44'-0"
Open (With Side Guides)
Evaluated Without Artificial Bottom Seal
8'-0" 50'-0"
aTotal Plan Length is the sum of the width of all curtain panels.
b Passage doors may be added when the minimum total plan length is increased beyond the values stated above at a rate of 4 feet per passage door.

MAXIMUM SIZE LIMITATIONS (FIRE-RATED ASSEMBLIES)
Certification Procedure Maximum Areaa Maximum Dimensionsa
LABEL (Tested) - Individual Panel 7.28 m2
78.4 sq ft
2.6 m Wide x 2.8 m High
8'-6" Wide x 9'-2" High
LABEL (Tested) - Complete Assembly 17.2 m2
185 sq ft
6.14 m Total Plan Lengthb x 2.8 m High
20'-2" Total Plan Lengthb x 9'-2" High
CERTIFICATE/LABEL  Unlimitedc Unlimitedc
aThe size limitation is based on a three-sided assembly tested with two 1.77 m wide by 2.8 m high sides and a front face 2.6 m wide by 2.8 m high.
bTotal Plan Length is the sum of the width of all curtain panels.
cThe AHJ may approve oversize doors with no size limitation based on an oversized certificate/label that states the door supplied is constructed in accordance with the certified design except for the size.

 
Listing Report Certificate of Compliance Return to Search
Attributes
Certificate Date of ExpiryDecember 31, 2026
Certificate Date of Initial RegistrationAugust 04, 2023
Certificate NumberWHI23-11025806
CriteriaNFPA 252 (2012)
CriteriaUL 1784 (2015)
CriteriaUL 10(d) (2014)
CriteriaUL 10(c) (2016)
CriteriaUL 10(b) (2008) (R2015)
CSI Code08 30 00 Specialty Doors and Frames
Fire Resistance20 Min w/out Hose Negative Pressure
Fire Resistance20 Min w/out Hose Positive Pressure
Fire Resistance3 Hour Positive Pressure
Listing SectionDOORS
Spec ID32891
Design Documents
No Results
Public Documents
No Results