Intertek Directory of Building Products

3M FireDam™ Spray 100 Company: 3M Company

This product is a spray applied liquid used to seal voids in fire resistant assemblies. This product has been tested as an integral part of a perimeter joint protection (fire resistive joint system).

 

Tests

ISMA Fire Test

ASTM E 1399 Cycling

UL 2079 Air Leakage

 

Reference Listed Design Section 

Design No.

Nom Width (Inches)

Movement Capability
of Joint System

Fire Resistance Ratings

% Movement

Cycles

Rate

T (minutes) 

F (minutes)

L (SCFM)

CEJ 113 P

8

 ± 16.7%

500 

 30

15 

120 

 < 1

CEJ 114 P

8

 ± 16.7%

500 

 30

 15

 120

 < 2

CEJ 115 P

8

 ± 16.7%

 500

 30

 15

 120

 < 1

CEJ 116 P

8

 ± 16.7%

 500

 30

 15

 120

 < 1

CEJ 119 P

8

 ± 16.7%

 500

 30

 15

 120

 < 1

CEJ 120 P

8

 ± 16.7%

 500

 30

 15

 120

 < 2

CEJ 121 P

8

± 16.7% 

 500

 30

 15

 120

 < 2

CEJ 122 P

8

± 16.7% 

 500

 30

 15

 120

 < 1

CEJ 123 P

8

± 16.7% 

 500

 30

 15

 120

 < 1

CEJ 124 P

8

± 16.7% 

 500

 30

 15

 120

 < 1

CEJ 125 P

8

 ± 16.7%

 500

 30

 15

 120

 < 1

CEJ 126 P

8

 ± 16.7%

 500

 30

 15

 120

 < 1

CEJ 158 P

8

± 16.7% 

 500

 30

 120

 < 1

CEJ 159 P

8

± 16.7% 

 500

 30

0

120 

 < 2

CEJ 160 P

8

± 16.7%Horizontal ± 6.25%Vertical Shear 

500 

 30

 150

 180

< 1 

CEJ 161 P

8

 ± 16.7%Horizontal ± 6.25%Vertical Shear 

 500

 30

 150

 180

< 1 

CEJ 163 P

8

± 16.7% 

 500

 30

 120

 < 2

CEJ 164 P

8

± 16.7% 

 500

 30

0

 120

 < 2

CEJ 165 P

8

± 16.7%Horizontal ± 6.25%Vertical Shear 

 500

 30

150 

 180

 < 1

CEJ 166 P

8

± 16.7%Horizontal ± 6.25%Vertical Shear 

 500

 30

150 

 180

 < 1.0

CEJ 167 P

8

± 16.7%Horizontal ± 6.25%Vertical Shear 

 500

30 

150

 180

 < 1.0

CEJ 168 P

8

± 16.7%Horizontal ± 6.25%Vertical Shear 

 500

 30

 150

 180

 < 1.0

CEJ 169 P

8

 ± 16.7%Horizontal ± 6.25%Vertical Shear

 500

 30

 150

180 

 < 1.0

CEJ 234 P

8

 ± 10 %Horizontal ± 6.25%Vertical Shear

 500

 30

 15

60 

   < 1.0

CEJ 238 P

8

 0 %

N/A 

N/A 

 90

180 

< 1.0 

CEJ 266 P

6

 ± 10 %Horizontal ± 6.25%Vertical Shear

 500

30 

45 

 120

 < 1.0

CEJ 267 P

6

± 10 %Horizontal ± 6.25%Vertical Shear 

 500

 30

 45

 120

 < 1.0

CEJ 288 P

8

± 16.7%

Horizontal

± 6.25%Vertical Shear

 500

 30

 15

 120

 < 1.0

CEJ 289 P

8

 ± 16.7%Horizontal ± 6.25%Vertical Shear

500 

 30

 15

120 

 < 1.0

CEJ 295 P

8

± 16.7%Horizontal ± 6.25%Vertical Shear 

 500

 30

150 

180 

 < 1.0

CEJ 311 P

8

± 16.7%Horizontal ± 6.25%Vertical Shear 

 500

30 

150 

 180

 < 1.0

CEJ 312 P

8

 ± 16.7%Horizontal ± 6.25%Vertical Shear

500 

 30

 150

180 

 < 1.0

CEJ 313 P

8

 ± 16.7%Horizontal ± 6.25%Vertical Shear

 500

 30

 120

 120

 < 1.0

CEJ 370 P

8 1/2

± 0%Horizontal ± 0%Vertical Shear

500

30

60

120

< 1

 

 

Listing Report Return to Search
Attributes
CriteriaISMA Fire Test
CriteriaUL 2079 Air Leakage (2004)
CriteriaASTM E1399 Cycling
CSI Code07 80 00 Fire and Smoke Protection
CSI Code07 84 43 Fire-Resistant Joint Sealants
Listing SectionFIRESTOP SYSTEMS
Spec ID13540
Design Documents
Design No CEJ 113 P Perimeter Fire Barrier System
Design No CEJ 114 P Perimeter Fire Barrier System
Design No CEJ 115 P Perimeter Fire Barrier System
Design No CEJ 116 P Perimeter Fire Barrier System
Design No CEJ 119 P Perimeter Fire Barrier System
Design No CEJ 120 P Perimeter Fire Barrier System
Design No CEJ 121 P Perimeter Fire Barrier System
Design No CEJ 122 P Perimeter Fire Barrier System
Design No CEJ 123 P Perimeter Fire Barrier System
Design No CEJ 124 P Perimeter Fire Barrier System
Design No CEJ 125 P Perimeter Fire Barrier System
Design No CEJ 126 P Perimeter Fire Barrier System
Design No CEJ 158 P Perimeter Fire Barrier System
Design No CEJ 159 P Perimeter Fire Barrier System
Design No CEJ 160 P Perimeter Fire Barrier System
Design No CEJ 161 P Perimeter Fire Barrier System
Design No CEJ 163 P Perimeter Fire Barrier System
Design No CEJ 164 P Perimeter Fire Barrier System
Design No CEJ 165 P Perimeter Fire Barrier System
Design No CEJ 166 P Perimeter Fire Barrier System
Design No CEJ 167 P Perimeter Fire Barrier System
Design No CEJ 168 P Perimeter Fire Barrier System
Design No CEJ 169 P Perimeter Fire Barrier System
Design No CEJ 234 P Perimeter Fire Barrier System
Design No CEJ 238 P Perimeter Fire Barrier System
Design No CEJ 266 P Perimeter Fire Barrier System
Design No CEJ 267 P Perimeter Fire Barrier System
Design No CEJ 288 P Perimeter Fire Barrier System
Design No CEJ 289 P Perimeter Fire Barrier System
Design No CEJ 295 P Perimeter Fire Barrier System
Design No CEJ 311 P Perimeter Fire Barrier System
Design No CEJ 312 P Perimeter Fire Barrier System
Design No CEJ 313 P Perimeter Fire Barrier System
Design No CEJ 370 P Perimeter Fire Barrier System
Public Documents