Specifications |
|
|
|
|
|
|
|
|
|
|
|
|
Door Size |
Door Thickness |
Core Thickness |
Stiffeners |
Single Swing: 4'0"wide x 7'2"high1 |
Minimum 1-3/4" ± 1/16" |
Minimum 1-1/2" |
18 GA Steel C-Channel |
Pairs: 8'0"wide x 7'2"high1 |
Minimum 1-3/4" ± 1/16" |
Minimum 1-1/2" |
18 GA Steel C-Channel |
Double Egress: Not Allowed. |
Not Applicable. |
Not Applicable. |
Not Applicable. |
|
[1] Maximum height increases to 10'0" for doors rated up to 90 minutes. Minimum 3 point latching for std. pairs.
Vision Panel:
Rating |
Max Area (Visible) |
Max Height (Visible) |
Max Width (Visible) |
20/45 Minute |
1296 sq. in. |
54" |
30" |
60/90 Minute |
100 sq. in. |
33" |
10" |