Intertek Directory of Building Products

Total Door Cat. C Fire Window Frames w/ Pemko FG3000 & Pilkington Glass Company: Total Door II, Inc.

Pressed Steel Fire Window Frame (14, 16 gauge) (Welded Up) for installation in 1 hour locations in steel/wood stud drywall or masonry openings.

Limitations: "Firelite" listed glazing or equivalent must be used. Prior approval must be obtained from the Authority Having Jurisdiction as applicable code requirements may vary. All listing conditions for glazing must be satisfied.


Sizes and Ratings for Visible Glazing:


Maximum Clearview Sizes
Applications
Fire Rating
Total Area
Width
Height
Stop
Height
Steel Door Vision Panels
20 min. 2856 sq.in. 34" 81" 0.625
Steel Door Vision Panels 45 min 2856 sq.in. 34" 84" 0.625
Steel Door Vision Panels 60 & 90 min. 1716 sq.in. 12" 46" 0.625
Windows/ Transoms
20 & 45 min. 3528 per panel 98" 36" 0.625
Sidelights
20 & 45 min. 4608 per panel 48" 96" 0.625

Note: Code requirements may limit use in applications involving fire ratings of 1 hour or greater duration. Such use is subject to the approval of the Authority Having Jurisdictions. The aforementioned values are applicable solely for fire ratings.

Frame Details (for Transom/Sidelight/Fire Window Frames):

Total Maximum Width: 12'8" drywall, 13'6" masonry
Total Maximum Height: 11'4" drywall, 12'0" masonry
Material: 16 gauge steel (0.060" ± 0.007)
Construction: Welded construction (K-D frames are not acceptable)
Stop Height: 5/8"
Glazing Beads: 18 Gauge Steel (0.048 ± 0.007)
Glazing Compound: Pemko's Fireglaze Compound (FG3000)
Glass: Pilkington's 1/4" (6.4mm) Georgian or Diamond Polished Wire Glass


Evaluated to the following:


Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:


ASTM-E163, Methods of Fire Tests of Fire Window Assemblies.

CAN/ULC-S106, Standard Method for Fire Tests of Window & Glass Block Assemblies.

NFPA-257, Standard Method for Fire Tests of Fire Window Assemblies.

UBC-7-4-94, Uniform Building Code.

UL-9, Fire Tests of Window Assemblies.
and are installed, unless otherwise noted, in accordance with the following:

NFPA-80, Fire Doors & Windows.


Manufacturer's Instructions:


Listed maximum sizes of lights are based on sizes tested and may exceed local code requirements.

All assemblies are identified by a label or marking bearing the wording "Listed Fire Window Frame", a time interval, a serial number and the WHI Certification Mark.

Listing Report Return to Search
Attributes
CriteriaASTM E163 (1984)
CriteriaNFPA 257 (2000)
CriteriaUL 9 (2000)
CriteriaUBC 7-4 (1994)
CriteriaNFPA 80 (1995)
CSI Code08 11 00 Metal Doors and Frames
Fire Resistance45 Min Neutral Pressure
Fire Resistance90 Min Neutral Pressure
Fire Resistance60 Min Neutral Pressure
Fire Resistance20 Min PP Category C Proprietary Frame
Fire Resistance45 Min PP Category C Proprietary Frame
Fire Resistance60 Min PP Category C Proprietary Frame
Fire Resistance90 Min PP Category C Proprietary Frame
Fire Resistance20 Min Neutral Pressure
Listing SectionCATEGORY C - PROPRIETARY FRAMES
Spec ID15571