Non-Comb. Deck (AN-24)
Slope: 2-1/2:12
-
Optional - One (1) ply of HPR Glasbase, HPR Premium Glasbase, or ASTM D4601 Type II base sheet
-
1/2" thick DensDeck, mechanically fastened
-
One (1) ply of HPR Torch Base, heat welded.
-
StressPly IV Plus, heat welded.
-
Surfaced with a flood coat of ASTM D312 roofing asphalt, Garlastic KM Plus, WeatherScreen, or Black-Knight Cold. Embedded with roofing gravel at a minimum 400 pounds per roofing square.
Note: The component materials of each system must be applied in the order in which they are listed above.
Evaluated to the following:
The roof covering systems in this section have been evaluated for external fire resistance Classifications A, B, C as outlined by the following test methods:
- ASTM-E108 - American Society for Testing & Materials 'Standard Methods of Fire Test of Roof Covering'
- ULC-S107 - Underwriters' Laboratories of Canada 'Standard Method of Tests for Fire Resistance of Roof Covering Materials'
- UL-790 - Underwriters' Laboratories Inc. 'Tests for Fire Resistance of Roof Covering Materials'
Each system listing identifies the deck substrate as either non-combustible or combustible. Systems evaluated for combustible decks will provide the same ratings when applied over non-combustible decks. Unless otherwise noted in individual listings, combustible decks shall be sheathed with a minimum 15/32" veneer plywood or minimum 7/16" non-veneer APA rated sheathing panel (oriented strand board panels, structural particleboard panels, composite panels or wafer-board panels) or 3/4" thick solid wood sheathing boards. The component materials of each system must be applied in the order in which they are listed. All components of the system must be listed for external fire exposure by an agency acceptable to the AHJ.
Some Roof Covering Systems have been evaluated for other performance characteristics, in addition to external fire exposure. Where applicable, such additional performance characteristics are noted within the specific listing.
In all cases, manufacturer's instructions should be consulted for installation procedures and details not covered by these listings.
Listed Materials are identified by a label or marking bearing the wording, "Listed Roofing Component", a reference number or code and the WHI Certification Mark.