Hope's Windows Jamestown-175 Series 45 Minute Door and Window Frame Assemblies
Company: Hope's Windows, Inc.
CATEGORY D - DOOR/FRAME ASSEMBLIES
Jamestown-175 Series Door/Frame Assemblies. Hot Rolled Steel Fire Doors and Frames shall have minimum web thickness of .160" and .141" flange thickness, corners to be welded. For installation in 3/4 hour locations in steel/wood stud drywall or masonry openings. These fire door/frame assemblies may also incorporate Legacy 175 Series Window Assemblies as transoms or sidelights with steel mullions between.
Limitations: #1000HD mortise hinges; #454 Ives Surface bolts at head and sill of inactive leaf.
| Configuration |
Maximum Size |
| Assembly Opening (including Sidelights & Transoms) |
13'7-1/2" wide x 10'11-1/2" high |
| Single Swing |
3'6" wide x 8'0" high |
| Standard Pairs |
7'0" wide x 8'0" high |
| Single Swing with Integral Transom |
3'6" wide x 10'11" high |
| Standard Pairs with Integral Transom |
7'0" wide x 10'11" high |
| Transom |
3'6" wide x 2'11" high |
 |
7'0" wide x 2'11" high |
| Vision Panels in Door |
| Maximum Clear View Dimensions: |
| The following maximum dimensions are Hope's limitations for glass. The final size must be determined between the glass manufacturer's size limitations & Hope's limitations. |
| Maximum Clear View Dimensions for a Single Panel: |
| Maximum Width |
36-13/16" |
| Maximum Height |
47-11/16" |
| Maximum Total Glazing Area |
1755 sq.in. |
Evaluated to the following:
This category includes doors and frames that are labeled as an assembly. See Positive Pressure Section Header for more information.
FIRE WINDOW FRAMES
Jamestown-175 Series Window Assemblies. Hot Rolled Steel Fire Window Frames (minimum thickness .160" @ webs & .141" # flanges), welded corners. Windows may be fixed or operable for installation in 3/4 hour locations in steel/wood stud drywall or masonry openings. These assemblies may also incorporate the Legacy 175 Series Door/Frame Assemblies or 5000 Series Door/Frame Assemblies with steel mullions between.
| Maximum Overall Dimensions: |
| Width |
163-1/2" |
| Height |
131-1/2" |
| Maximum Sash (Fixed) Window Dimensions: |
| Maximum Assembly Width |
99-1/4" |
| Maximum Assembly Height |
131" |
| Maximum Sash Area |
55 sq.ft. |
| Maximum Ventilator (Operable) Window Dimensions: |
| Side Hinged |
 |
| Maximum Width |
38-1/8" |
| Maximum Height |
72-3/8" |
| Top Hinged |
 |
| Maximum Width |
58-3/8" |
| Maximum Height |
60-1/8" |
| Maximum Clear View Dimensions: |
| The following maximum dimensions are Hope's limitations for glass. The final size must be determined between the glass manufacturer's size limitations and Hope's limitations. |
| Maximum Clear View Dimensions for Single Panel |
| Maximum Width |
58-5/8" |
| Maximum Height |
95-3/16" |
| Maximum Clear View Area |
4164 sq.in. |
| No combinations of width and height dimensions can exceed 4164 sq.in. |
Evaluated to the following:
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
UL 10C, Positive Pressure Fire Test of Door Assemblies.
NFPA 252, Fire Test of Door Assemblies.
CAN/ULC S104, Standard Method for Fire Test of Door Assemblies.
CAN/ULC S106, Standard Method for Fire Tests of Window & Glass Block Assemblies.
NFPA 257, Standard Method for Fire Tests of Fire Window Assemblies.
UL 9, Fire Tests of Window Assemblies.
and are installed, unless otherwise noted, in accordance with the following:
NFPA-80, Fire Doors & Windows.
Manufacturer's Instructions.
Listed maximum sizes of lights are based on sizes tested and may exceed local code requirements.
All assemblies are identified by a label or marking bearing the wording "Listed Fire Window Frame", a time interval, a serial number and the WHI Certification Mark.