Extruded Aluminum Fire Window Frame (TRIMSTYLE*) (Knock-Down) for use as a borrowed light for installation in 20 minute locations (without Hose Stream) in steel/wood stud drywall or masonry openings.
Limitations: Requires listed glazing/Glazing Sealant - Metacaulk 990** or 100% Pure Silicone Caulk can be used.
| Minimum Throat Opening: |
3-3/4" |
| Maximum Clear Area: |
2,880 sq.in. |
| Maximum Height: |
48" |
| Maximum Width: |
60" |
Extruded Aluminum Fire Window Frame (TRIMSTYLE*) (Knock-Down) for use as a borrowed light for installation in 20 minute locations (without Hose Stream) in steel/wood stud drywall or masonry openings.
Limitations: Requires listed glazing/Glazing Sealant - Metacaulk 990** or 100% Pure Silicone Caulk can be used.
| Minimum Throat Opening: |
3-3/4" |
| Maximum Clear Area: |
5,184 sq.in. |
| Maximum Height: |
108" |
| Maximum Width: |
48" |
*Manufacturer's Designation
**A listed product of Metalines Corporation
Evaluated to the following:
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
ASTM-E163, Methods of Fire Tests of Fire Window Assemblies.
CAN/ULC-S106, Standard Method for Fire Tests of Window & Glass Block Assemblies.
NFPA-257, Standard Method for Fire Tests of Fire Window Assemblies.
UBC-7-4-94, Uniform Building Code.
UL-9, Fire Tests of Window Assemblies.
and are installed, unless otherwise noted, in accordance with the following:
NFPA-80, Fire Doors & Windows.
Manufacturer's Instructions.
Listed maximum sizes of lights are based on sizes tested and may exceed local code requirements.
All assemblies are identified by a label or marking bearing the wording "Listed Fire Window Frame", a time interval, a serial number and the WHI Certification Mark.