Hollow Metal Type (16,18, 20 gauge)(Steel-Faced) (Honeycomb Core) Swinging Flush Design Fire Door for installation singly in 90 minute - 3 hour locations or pairs for 90 minutes.
Maximum Size Openings:
Single - 3' 4" x 8' 0" ( 3 hour), 4' 0" x 8' 0" ( 90 minute)
Pair - 8'0" wide x 8'0" high (90 minute) Three point latching required.
Double Egress - not allowed
Vision Panel:
- Max. Area: 1296 sq. in.
- Max. Height: 54"
- Max. Width: 30"
- Max. Duration for 1296 sq. in. is 90 min.
- Glazing frame must be a listed metal glazing frame.
- Glazing must be listed for size and duration.
Limitations: Cylindrical/Mortise Latches/Deadbolts/Mortise or Surface Mounted Vertical Rod or Rim Type Fire Exit Hardware
Unless otherwise noted, these doors have been evaluated for conformance to the following standards listed below for both positive and neutral pressure fire tests:
UBC 7-2 Methods of Fire Tests of Door Assemblies
UL 10C Positive Pressure Fire Tests of Door Assemblies
NFPA 252 Standard Methods of Fire Tests of Door Assemblies
ASTM E2074 Methods of Fire Tests of Door Assemblies, Including Positive Pressure Testing of Side Hinged and Pivoted Swinging Door Assemblies
CAN S104 Standard Methods of Fire Tests of Door Assemblies
Labeled doors must include installation instructions to be furnished by the door labeler manufacturer.