Intertek Directory of Building Products

Hager Category H Smoke and Draft Control Gaskets Company: Hager Companies

CATEGORY H - SMOKE & DRAFT CONTROL GASKETS
Gasket (Models 726, 736, 737, 739S 785S, 860S, 862S, 863S, 881S, 885S, 890S, 891S, 892S, 896S, 800S, 802S, 803S, 808S, 882S, 893S, 858S, 859S, 861S, 864S, 865S, 866S, 870S, 871S, 873S, 875S, 877S, 878S, 880S, 887S, 836S, 837S, 844S, 874S, 756S, 802S, 872S, 882S, and 884S) for installation with Listed Wood or Mineral Core Fire Doors with Listed Steel or Wood Fire Door Frames, and Listed Steel (Steel-Stiffened, Polystyrene, Urethane or Honeycomb) or Wood Fire Doors with Listed Steel Fire Door Frames. Listed Category "H" Smoke & Draft Control Gaskets used for astragals shall be used on the meeting edge of pairs of doors.
Configuration Maximum Size
Single Swing 4'0" wide x 10'0" high
Pairs 8'0" wide x 10'0" high
 
Specifctions for S739 Gasket
Door Type  Wood Steel
Maximum Ambient leakage @0.30In H20 0.46 SCFM/ft2 0.46 SCFM/ft2
Maximum Elevated Leakage  @0.30In H20 0.60 SCFM/ft2 0.41 SCFM/ft2
Closing Force 12lbs 14lbs
Listing Report Return to Search
Attributes
CriteriaCAN4 S104 (1985)
CriteriaUL 10(c) (2009)
CriteriaUL 1784 (2015)
CriteriaUL 10(c) (2016)
CSI Code07 86 00 Smoke Seals
Fire Resistance20 Min Category H Smoke & Draft Control Gasket
Fire Resistance45 Min Category H Smoke & Draft Control Gasket
Fire Resistance60 Min Category H Smoke & Draft Control Gasket
Fire Resistance90 Min Category H Smoke & Draft Control Gasket
Fire Resistance3 Hour Category H Smoke & Draft Control Gasket
Listing SectionCATEGORY H - SMOKE & DRAFT CONTROL GASKETING
Smoke and Draft ControlSmoke Leakage < 3 cfm/sq ft per UL 1784
Spec ID19756
Design Documents
No Results
Public Documents
No Results