Deansteel 20-180 Min Steel Fire Door with Composite Core-Temp Rise 250 Degrees PP Company: Deansteel Manufacturing Company, Inc.

Steel-Faced (16, 18, 20 gauge) (Mineral Core Type) Swinging Flush Door for installation in 180 minute locations. For use in listed (3-sided) 16 gauge welded steel frames meeting ANSI-A155.1/UL-63 or as per frame manufacturer's listing(s).

 

Limitations*: Mortise or Cylindrical Latches with Maximum 5" Backset/Mortised Exit Devices/Surface-Mounted Vertical Rod Fire Exit Devices/Rim-Type Fire Exit Devices/Concealed Vertical Rod Exit Devices/Deadbolts/Extension Bolts with a maximum extension of 24"/Surface Bolts/Automatic Flush Bolts/Surface-Mounted Closers/Surface-Mounted Protection Plates/Viewer/Pocket Pivot Hinges/Open-Back Strikes/Louver/Electric Raceway/Vision Light Kit - Maximum 1296 sq.in. (20 & 45 minute); Maximum 100 sq.in. (60 & 90 minute)/Surface-Mounted or Mortised Door Bottoms/Astragal Required/Temperature Rise - 250°F at 30 minutes.

 

Configuration

Maximum Size*

Single Swing:

4'0" wide x 8'0" high

Standard Pairs:

8'0" wide x 8'0" high

Double Egress Pairs:

8'0" wide x 7'2" high

 

*See manufacturer's installation instructions for additional information on Smoke & Draft Control, size restrictions and limitations.
Testing Standard: UBC-7-2-97/UL-10C (Positive Pressure).

Evaluated to the following...

This category includes doors evaluated without an edge-sealing system between the door and frame. It also includes doors evaluated with a sealing system incorporated (concealed or visible) into the edge of the door by the licensed manufacturer or machining distributor.

 

Meeting edges of pairs may require an astragal or an edge-sealing system. Please refer to individual door listings.

These doors are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in the accordance with the frame manufacturer's individual listing.

All doors listed in Category A are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.

 

All doors in this category are identified by a label or marking bearing the wording, "Listed Fire Door", a time interval, a temperature rise rating, a serial number and the Warnock Hersey Certification Mark and "UBC-7-2-97/UL 10C".

 

Listing Report Return to Search
Attributes
CriteriaUBC 7-2 (1997)
CriteriaUL 10(c) (1998) (R2001)
CriteriaUL 10(c) (2009)
CSI Code08 11 00 Metal Doors and Frames
CSI Code08 11 13 Hollow Metal Doors and Frames
Fire Resistance20 Min w/out Hose Stream PP Cat A Door
Fire Resistance45 Min Neutral Pressure
Fire Resistance60 Min PP Category A Door
Fire Resistance90 Min Neutral Pressure
Fire Resistance2 Hour Neutral Pressure
Fire Resistance3 Hour Neutral Pressure
Fire Resistance3 Hour PP Category A Door
Fire ResistanceNeutral Pressure
Listing SectionCATEGORY A - DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Spec ID19857
SwingSingle Swing
SwingStandard Pairs
SwingDouble Egress