Intertek Directory of Building Products

Taylor Entrance Systems 20 Min w/out hose Hollow Metal Fire Door Company: Taylor Entrance Systems

CATEGORY B - DOORS - ADDITIONAL EDGE-SEALING SYSTEM REQUIRED 
  • Uni-Door/Royal Steel-Faced (22, 24 gauge) (Urethane Core) (Simulated Panel or Flush Type) Swinging Flush Door for installation in 20 minute (without hose stream) locations. For use in any "Category C - Standard frame. These doors may also be installed in frames listed in "Category C - Proprietary" in accordance with the frame manufacturer's individual listing. A field-applied edge seal system is required. Refer to the individual manufacturer's Category G listing for limitations.  
  • Regal/Regency with Stainable Steel, Steel-Faced (22, 24 gauge) (Urethane Core) (Simulated Panel or Flush Type) Swinging Flush Door for installation in up to 90 minute (without hose stream) locations. For use in any "Category C - Standard frame. These doors may also be installed in frames listed in "Category C - Proprietary" in accordance with the frame manufacturer's individual listing. A field-applied edge seal system is required. Refer to the individual manufacturer's Category G listing for limitations. 
  • Durador/Simplicity Steel-Faced (22, 24 gauge) (Urethane Core) (Simulated Panel or Flush Type) Swinging Flush Door for installation in 20 minute (without hose stream) locations. For use in any "Category C - Standard frame. These doors may also be installed in frames listed in "Category C - Proprietary" in accordance with the frame manufacturer's individual listing. A field-applied edge seal system is required. Refer to the individual manufacturer's Category G listing for limitations.
Limitations*
Mortise or Cylindrical Latches with maximum 5" Backset/Mortised Exit Devices/Surface Mounted Vertical Rod Fire Exit Devices/Rim-Type Fire Exit Devices/Deadbolts/Surface-Mounted Closers/Viewer/Surface-Mounted Door Bottoms. Temperature Rise - 650°F at 30 minutes. 
Maximum Size
SINGLE SWING                  3'-6" wide x 7'-0" high
STANDARD PAIRS              Not Allowed
DOUBLE EGRESS PAIRS   Not Allowed 
 
*See manufacturer's installation instructions for additional information on Smoke and Draft Control, size restrictions and limitations.
Testing Standards
UL-10C (Positive Pressure) 
Evaluated to the following...
This category includes doors evaluated with an edge-sealing system (Category G) field-applied to the labeled frame or door. The application of the edge-sealing system does not require any machining of the frame or door. Please refer to "Category G - Edge-Sealing System" for individual manufacturer's listings.
 
These assemblies are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in the accordance with the frame manufacturer's individual listing.
 
All doors listed in Category B are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.
 
All doors in this category are identified by a label or marking bearing the wording, "Listed Fire Door", a time interval, a temperature rise rating, a serial number and the Warnock Hersey Certification Mark and "UL 10C".
MODELS AND DESCRIPTIONS
 
  PERMA DOOR TAYLOR DOOR
Lite Gauge Door Economy Economy
Adjustable Hinge Royal Uni-Dor
Fixed Hinge Simplicity DuraDoor
Stainable Steel Regency Regal
Listing Report Return to Search
Attributes
CriteriaNFPA 252 (2017)
CriteriaUL 10(c) (2016) Ed. 3 (R:27 May 2021)
CSI Code08 11 00 Metal Doors and Frames
CSI Code08 11 13 Hollow Metal Doors and Frames
Fire Resistance20 Min w/out Hose Stream NP
Fire Resistance20 Min w/out Hose Stream PP Cat B Door
Listing SectionCATEGORY B - DOORS - ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Spec ID21245
SwingSingle Swing
Temperature Rise@ 30 Min = 650° F MAX Where Lites Do Not Exceed 100 IN2