Intertek Directory of Building Products

ABS 20 Min Wood Flush Fire Door - Cat. A & Cat. B Company: American Building Supply, Inc.

CATEGORY A DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED:
Wood Core Type (Particle Board Core), Swinging Flush Design Fire Door with Inlay Moulding for installation singly or in pairs in 20 minute locations (without Hose Stream Test) for use in any Category C Standard Frames.

This category includes doors evaluated without an edge-sealing system between the door and frame. It also includes doors evaluated with a sealing system incorporated (concealed or visible) into the edge of the door by the licensed manufacturer or machining distributor. Meeting edges of pairs may require an astragal or an edge-sealing system. 

Limitations: Cylindrical and Mortise Latches with 2-3/4" backset/Surface or Mortised Automatic or Manual Top and Bottom Flush Bolts/Surface Mounted Vertical Rod Fire Exit Hardware/Surface Mounted Closer/Automatic Door Bottoms/Vinyl Veneer Covering.
Configuration Maximum Size
Single 4'0" wide x 9'0" high
Pair 8'0" wide x 9'0" high
Double Egress 8'0" wide x 9'0" high

Limitations: VingCard Essence Mortise Single Point Lock
Configuration Maximum Size
Single 4'0" wide x 8'0" high
Pair N/A
Double Egress N/A

CATEGORY B - DOORS - ADDITIONAL EDGE-SEALING SYSTEM REQUIRED:
Wood Core Type (Particle Board Core), Swinging Flush Design Fire Door with Inlay Moulding for installation singly or in pairs in 14, 16 gauge labeled steel door frames for 20 minute locations (without Hose Stream Test) using a field applied edge-sealing system. For use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in accordance with the door manufacturer's installation instructions.

This category includes doors evaluated with an edge-sealing system (Category G) field-applied to the labeled frame or door. The application of the edge-sealing system does not require any machining of the frame or door. Please refer to "Category G - Edge-Sealing System" for individual manufacturer's listings. All doors listed in Category B are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.

Limitations: Cylindrical and Mortise Latches to 2-3/4" Backset/Surface or Mortised Automatic or Manual Top and Bottom Flush Bolts/Surface Mounted Vertical Rod Fire Exit Hardware/Surface Mounted Closer/Automatic Door Bottoms/Vinyl Veneer Covering.
Configuration
Maximum Size
Single 4'0" wide x 9'0" high
Pairs 8'0" wide x 9'0" high
Double Egress 8'0" wide x 9'0" high


* See manufacturer's installation instructions for additional information, restrictions and limitations.
* Particle board includes LSL, Stave, Particle board, Agri Core.  Minimum core density 25 pcf.
* Includes 1-3/4" doors only.
* Solid core wood doors which have flush construction only.  No Profile core doors. All other multiple component laminated core designs, such as but not limited to multi-component acoustical door designs, are not allowed.
* Standard mortise hardware does not require intumescent in the mortise pocket. 
* Intertek does not certify the hardware or any electrified hardware used in this listing.  Intertek is approving the cutout only.


Evaluated to the following:

All doors are identified by a label or marking bearing the wording, "Listed Fire Door", a time interval,  a serial number and the Warnock Hersey Certification Mark and "UL 10C".
Listing Report Return to Search
Attributes
CriteriaUL 10(c) (2016) Ed. 3 (R:27 May 2021)
CriteriaNFPA 252 (2022)
CSI Code08 10 00 Doors and Frames
Fire Resistance20 Min w/out Hose Stream PP Cat A Door
Fire Resistance20 Min w/out Hose Stream PP Cat B Door
Listing SectionCATEGORY B - DOORS - ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Listing SectionCATEGORY A - DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Spec ID22190
SwingSingle Swing
SwingStandard Pairs
SwingDouble Egress
Design Documents
No Results
Public Documents