DOOR FRAMES
Pressed Steel Door Frame (14 or 16 gauge) (Welded Up) for installation in 3 hour masonry openings.
Maximum Size of Openings: |
Singles- 4'0" wide x 10'0" high Pairs - 8'0" wide x 10'0" high Double Egress Pairs - 8'0" wide x 8'0" high |
Minimum Throat Opening: |
Singles & Pairs- 3-1/2" to 13" Double Egress Pairs- 3-3/4" to 13" |
Pressed Steel Door Frame (14 or 16 gauge) (Welded Up) (Single Unit Multiple Opening) for installation in 1-1/2 hour locations in steel/wood stud drywall or masonry openings.
Maximum Overall Size of Openings: |
12'8" wide x 8'0" high |
Maximum Size of Individual Openings: |
8'0" wide x 8'0" high |
Minimum Throat Opening: |
3-3/4" to 13" |
Pressed Steel Door Frame (14 or 16 gauge) (Welded Up or Knock Down) for installation in 1-1/2 hour locations in steel/wood stud drywall or masonry openings.
Maximum Size of Openings: |
Knock Down - Pairs- 8'0" wide x 8'0"- 4'0" wide x 8'0" high |
Throat Opening: |
3-5/8" to 9" |
Maximum Size of Openings: |
Welded Up - Singles- 4'0" wide x 10'0" high Welded Up - Pairs- 8'0" wide x 10'0" high |
Throat Opening: |
3-1/2" to 13" |
Maximum Size of Openings: |
Double Egress/Welded Up - Pairs- 8'0" wide x 8'0" high |
Throat Opening: |
3-3/4" to 13" |
Pressed Steel Door Frame (14 or 16 gauge) (Welded Up or Knock Down) for installation in 3/4 hour and 20 minute locations in steel/wood stud drywall or masonry openings.
Maximum Size of Openings: |
Knock Down - Singles- 4'0" wide x 8'0" high Knock Down - Pairs- 8'0" wide x 8'0" high |
Throat Opening: |
3-1/2" to 9" |
Maximum Size of Openings: |
Welded Up - Singles- 4'0" wide x 10'0" high Welded Up - Pairs-8'0" wide x 10'0" high |
Throat Opening: |
3-1/2" to 13" |
Maximum Size of Openings: |
Double Egress Welded Up - Pairs- 8'0" wide x 8'0" high |
Throat Opening: |
3-3/4" to 13" |
Pressed Steel Door Transom Panel Frame (14 or 16 gauge) (Welded Up) for installation in 1-1/2 hour locations in steel/wood stud drywall or masonry openings.
Maximum Overall Dimensions: |
Opening - 8'0" wide x 10'0" high Transom - 4'0" wide x 2'10" high or 8'0" wide x 2'8" high Opening - 4'0" wide x 10'0" high Transom - 4'0" wide x 4'2" high |
Minimum Throat Opening: |
3-1/2" to 13" |
Pressed Steel Door Frame with Transom Panels or Side Panels (14 or 16 gauge) (Welded Up) for installation in 1-1/2 hour locations in steel/wood stud drywall or masonry openings.
Maximum Overall Dimensions: |
Overall - 12'0" wide x 11'4" high Door Opening - 8'0" wide x 8'0" high Transom Panels - 3'0" wide x 4'0" high Side Panels - 2'9" wide x 4'6" high |
Minimum Throat Opening: |
3-1/2" to 13" |
Pressed Steel Door Frame with Transom or Side Lights or Panels (14 or 16 gauge) (Welded Up) for installation in 3/4 hour or 20 minute locations in steel/wood stud drywall or masonry openings.
Maximum Overall Dimensions: |
Overall - 12'0" wide x 11'4" high Door Opening - 8'0" wide x 8'0" high Each Light - 1296 sq.in. Transom Lights - 3'0" wide or 4'0" high Side Lights - 2'9" wide or 4'6" high Side Panels - 2'9" wide or 4'0" high Transom Panels - 3'0" wide or 4'0" high |
Minimum Throat Opening: |
3-1/2" to 13" |
Pressed Steel Door Frame with Transom Light (14 or 16 gauge) (Welded Up) for installation in 3/4 hour or 20 minute locations in steel/wood stud drywall or masonry openings.
Maximum Overall Dimensions: |
Overall - 4'0" wide x 10'0" high Door Opening - 4'0" wide x 10'0" high Each Light- 1296 sq.in. Transom Light - 4'0" wide or 4'0" high |
Minimum Throat Opening: |
3-1/2" to 13" |
Pressed Steel Door Frame with Glazed Transom and/or Side Light (14 or 16 gauge) (Welded Up) for installation in 20 minute without hose stream locations in steel/wood stud drywall or masonry openings.
Maximum Overall Dimensions: |
Overall - 13'2" wide x 11'7" high Door Opening - 8'0" wide x 10'0" high Each Light - 5268 sq.in. Each Light - 8'1-3/4" wide or 9'1-3/4" high |
Minimum Throat Opening: |
3-1/2" to 13" |
Evaluated to the following:
Unless otherwise noted, assemblies in this section have been tested to the following standards:
ASTM-E152, Methods of Fire Tests of Door Assemblies;
CAN/ULC-S104, Standard Method for Fire Tests of Door Assemblies;
NFPA-252, Standard Methods of Fire Tests of Door Assemblies;
UBC-7-2-94, Uniform Building Code;
UL-10(b), Fire Tests of Door Assemblies;
and are installed, unless otherwise noted, in accordance with the following:
NFPA-80, Fire Doors & Windows.
Manufacturer's Instructions.
Listed maximum sizes of lights are based on sizes tested and may exceed local code requirements.
All frames are identified by either a label or embossed marking bearing the wording "Listed (Product)" and the WHI Certification Mark. Frames rated for less than 3 hours also bear the time interval. Frame labels that do not include a time interval are rated for 3 hours.
FIRE WINDOW FRAMES
Pressed or Rolled Formed Steel Fire Window Frame (14, 16 gauge) (Welded Up) for installation in 3/4 hour or 20 minute locations in masonry openings.
Maximum Overall Dimensions: |
Overall: 12'0" wide x 11'4" high Each Light: 1,296 sq.in. Each Light: 3'3" wide or 4'0" high |
Minimum Throat Opening: |
3-1/2" to 13" |
Pressed or Roll Formed Steel Fire Widow Frame (14, 16 gauge) (Welded Up) for installation in 20 minute without hose stream locations in masonry openings.
Maximum Overall Dimensions: |
Overall: 13'2" wide x 9'7" high Each Light: 5,288 sq.in. Each Light: 9'1-3/4" wide or 9'1-3/4" high |
Minimum Throat Opening: |
3-1/2" to 13" |
Evaluated to the following:
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
ASTM-E163, Methods of Fire Tests of Fire Window Assemblies.
CAN/ULC-S106, Standard Method for Fire Tests of Window & Glass Block Assemblies.
NFPA-257, Standard Method for Fire Tests of Fire Window Assemblies.
UBC-7-4-94, Uniform Building Code.
UL-9, Fire Tests of Window Assemblies.
and are installed, unless otherwise noted, in accordance with the following:
NFPA-80, Fire Doors & Windows.
Manufacturer's Instructions.
Listed maximum sizes of lights are based on sizes tested and may exceed local code requirements.
All assemblies are identified by a label or marking bearing the wording "Listed Fire Window Frame", a time interval, a serial number and the WHI Certification Mark.
CATEGORY C - STANDARD FRAMES
Pressed Steel Door Frame (14, 16 gauge) for installation in up to 90 minute locations in steel/wood stud drywall or masonry openings.
Maximum Size of Openings: |
Singles: 4'0" wide x 10'0" high Pairs: 8'0" wide x 10'0" high Double Egress: 8'0" wide x 10'0" high |
Minimum Throat Opening: |
5" |
Pressed Steel Door Frame (14, 16 gauge) (Adjustable) for installation in up to 90 minute locations in steel/wood stud drywall or masonry openings.
Maximum Size of Openings: |
Singles 4'0" wide x 8'0" high |
Minimum Throat Opening: |
3-3/4" |
Testing Standard: UBC-7-2-97/UL-10C (Positive Pressure).
Evaluated to the following:
This category includes frames based on ANSI-A155.1/UL-63 and includes sidelight/transom assemblies. These frames are qualified for use in positive pressure assemblies, with Category A doors, or with Category B doors utilizing Category G edge-sealing systems. These frames, when installed in pairs in drywall construction, shall have anchors installed in the head section, minimum 24" o.c. These listings will not reference specific door types, as all door types are eligible.
All frames in this category are identified by a label or marking bearing the wording, "Listed Fire Door Frame", and the Warnock Hersey Certification Mark. Frames rated at less than 3 hours will have a time interval noted on the label/marking. See Positive Pressure Section Header for more information.