SAFTI FIRST SuperLite I-W Fire-Rated Wire Glass 20-90 Minute NEW Company: SAFTI FIRST

SuperLite I-W for installation in any listed door and/or "Category C-Standard" frame. Glazing techniques include listed fire-rated closed-cell foam tape, listed fire-rated ceramic glazing tape, 100% silicone caulking & PEMKO FG3000 "Fire Glaze".

Installations that require the use of Pemko FG3000 are indicated with "+". 

Superlite I-W (0.25") 20 Minute (with Hose Stream)

Clear View Dimension

Steel Doors

Wood Doors with Listed Vision Light Frame

Raised Side Lights

Transom Lights

Borrowed Lights/Windows

Max. Width

36"

36"

86"

96"

100"

Max. Height

92"

84"

106"

36"

106"

Max. Area

3289 sq.in.

2856 sq.in.

4608 sq.in.

3456 sq.in.

4608 sq.in.

Min. Stop Height

5/8"

5/8"

5/8"

5/8"

5/8"

  

Superlite I-W (0.25") 45 Minute (w/Hose Stream)

Clear View Dimension

Steel Doors

Wood Doors with Listed Vision Light Frame

Raised Side Lights

Transom Lights

Borrowed Lights/Windows

Max. Width

36"

36"

100"

96"

100"

Max. Height

84"

54"

100"

36"

100"

Max. Area

2856 sq.in.

1296 sq.in.

4608 sq.in.

3456 sq.in.

4608 sq.in.

Min. Stop Height

5/8"

5/8"

5/8"

5/8"

5/8"

 

Superlite I-W (0.25") 60 Minute (w/Hose Stream)

Clear View Dimension

Steel Doors

Wood Doors with Listed Vision Light Frame

Raised Side Lights

Transom Lights

Borrowed Lights/Windows

Max. Width

12"

12"

NA

NA

NA

Max. Height

46"

80"

NA

NA

NA

Max. Area

552 sq.in.

960 sq.in.

NA

NA

NA

Min. Stop Height

5/8"

5/8"

NA

NA

NA

 

Superlite I-W (0.25") 90 Minute (w/Hose Stream)

Clear View Dimension

Steel Doors

Wood or Steel Temp Rise Doors

Raised Side Lights

Transom Lights

Borrowed Lights/Windows

Max. Width

12"

10"

NA

NA

NA

Max. Height

46"

33"

NA

NA

NA

Max. Area

552 sq.in.

100 sq. in.

NA

NA

NA

Min. Stop Height

5/8"

5/8"

NA

NA

NA

 

Unless otherwise noted, these glazings have been evaluated for conformance to the following standards listed below:

When listed for use in a Door Vision Panel, Transom or Side Light:

ASTM E-152, Methods of Fire Tests of Door Assemblies
ASTM E-2074, Fire Tests of Door Assemblies Including Positive Pressure Testing of Side Hinged and Pivoted Swinging Door Assemblies
CAN4-S104(ULC-S104), Standard Method for Fire Tests of Door Assemblies
CSFM 43.7, Standard Methods of Fire Tests of Door Assemblies
NFPA 252, Standard Methods of Fire Tests of Door Assemblies
UBC 7-2-94, Uniform Building Code Standard
UL 10(b), Fire Tests of Door Assemblies
UL 10C, Positive Pressure Fire Tests of Door Assemblies

When listed for use in a Fire Window Assembly:

ASTM E-163, Methods of Fire Tests of Fire Window Assemblies
ASTM E-2010, Positive Pressure Fire Tests of Window Assemblies
CAN4-S106, Standard Method for Fire Tests of Window & Glass Block Assemblies
NFPA 257, Standard Method for Fire Tests of Fire Window Assemblies
UBC 7-4-94, Uniform Building Code Standard
UL 9, Fire Tests of Fire Window Assemblies

Listed products are intended to be installed, unless otherwise noted, in accordance with the following:

NFPA 80, Fire Doors & Windows

Manufacturer's Instructions

Listed maximum sizes of glazing are based on sizes tested and may exceed those allowed by local codes. Dependent on the end use installation, local codes may require that additional criteria be met to address considerations such as radiant heat hazards and impact safety. Under such circumstances, the prior approval of the Authority Having Jurisdiction must be obtained unless conformance to relevant additional requirements is indicated within the individual listing.

Clearance between the edges if the glazing and the inside edge of the frame shall not exceed 1/8" unless otherwise noted in the individual listing or the manufacturer's installation instructions.

All glazing is identified by an etched mark or label bearing the WHI Certification Mark or ETL Mark.

Listing Report Return to Search
Attributes
CriteriaNFPA 252 (1995)
CriteriaASTM E152-81a
CriteriaCSFM 43.7
CriteriaUBC 7-2 (1997)
CriteriaUBC 7-2 (1994)
CriteriaUL 10(b) (1997)
CriteriaUL 10(b) 2008 (R2009)
CriteriaUL 10(c) (2009)
CriteriaUL 10(c) (R2001)
CriteriaCPSC 16 CFR 1201 Category II (2004)
CriteriaASTM E2074 (2004)
CriteriaANSI Z97.1 (2004)
CriteriaNFPA 252 (2008)
CriteriaNFPA 257 (2007)
CriteriaASTM E2074 (2000)
CriteriaNFPA 257 (2000)
CriteriaUL 9 (2000)
CriteriaCAN4 S106 (1985)
CriteriaUBC 7-4 (1997)
CriteriaCAN4 S104 (1985)
CSI Code08 81 00 Glass Glazing
Fire Resistance45 Min Neutral Pressure
Fire Resistance90 Min Neutral Pressure
Fire Resistance60 Min Neutral Pressure
Fire Resistance45 Min Positive Pressure
Fire Resistance90 Min Positive Pressure
Fire Resistance60 Min Positive Pressure
Fire Resistance20 Min Neutral Pressure
Fire Resistance20 Min Positive Pressure
Frame OptionsListed Aluminum
Frame OptionsWood
Frame OptionsAny Rated System
Frame OptionsSteel
Listing SectionGLAZING/GLASS
Spec ID22398
STC RatingNone
Design Documents
No Results
Public Documents