Extruded Aluminum Door Frame (Fastrak II*) (Knock Down), with side light on one side only, for installation in 20 minute locations in steel/wood stud drywall openings tested without Hose Stream.
Limitations: Use with labeled 20 minute Fire Rated, Negative/Neutral Pressure Tested Single Swing, Flush Design Wood Door with stiles and rails. Cylindrical and Mortise Latches with 2-3/4" Backset. Pemko HSS2000 intumescent strip must be provided on doorframe. (See manufacturer's installation instructions).
Maximum Size |
64-1/2" wide x 108-1/2" high |
Wall Construction |
Steel/Wood Stud Drywall |
Min. Wall Thickness |
3-1/2" |
Max. Side Light Size |
Bottom: 912 sq.in.
Top: 1608 sq.in. |
Testing Standards: UBC 7-2-97/UL-10C (Positive Pressure).
Evaluated to the following:
This category includes frames not based on ANSI-A155.1/UL-63 construction Type (such as aluminum, wood, light gauge steel, composite, etc.). These listings will reference specific door types for which each frame is qualified. All frames listed in this section may be used in positive pressure assemblies per the terms and limitations of the individual listing.
All frames in this category are identified by a label or marking bearing the wording, "Listed Fire Door Frame", the Warnock Hersey Certification Mark, "UBC-7-2-97/UL-10C. Frames rated at less than 3 hours will have a time interval noted on the label/marking. See Positive Pressure Section Header for more information.