Intertek Directory of Building Products

Stainless Doors 20-90 Min Fire Doors PP w/hose Company: Stainless Doors Incorporated

Stainless Steel-Faced (14, 16, 18 gauge) Honeycomb, Expanded Polystyrene, or Urethane Core Swinging Flush Door for installation in up to 90 minute locations. For use in listed (3-sided) 16 gauge (14, 12 gauge) welded steel or stainless steel frames meeting UL-63 or per frame manufacturer's listing(s).

Limitations:
Mortise or Cylindrical Latches with maximum 5" backset/Mortise Exit Devices/Surface Mounted Vertical Rod Fire Exit Devices/Rim Type Fire Exit Devices/Concealed Vertical Rod Exit Devices/Deadbolts/Extension Bolts with a maximum extension of 12"/Surface bolts/Automatic Flush Bolts/Surface Mounted Closers/concealed Closer Arms/Surface Mounted Protection Plates/Viewer/Open-Back Strikes/Louver/Electric Raceway/Vision Light Kit/Surface Mounted or Mortised Door Bottoms/Astragal Required on All Pairs/Temperature Rise - Greater than 650°F at 30 minutes (Honeycomb, urethane, polyisocyanurate or expanded polystyrene core).  Maximum temperature rise - 250°F in 30 minutes (Proprietary Mineral Core).
Configuration Max. Size
Single Swing 3'0" wide x 8'0" high
Standard Pair 6'0" wide x 8'0" high
Double Egress N/A
Labeled Material Specifications 1-1/2 Hour 1 Hour 3/4 Hour
1/4" Wired Glass Area 100"2 100"2 1296"2
Width 12" 12" 54"
Height 33" 33" 54"
Listing Report Return to Search
Attributes
CriteriaUL 10(c) (1998)
CriteriaUBC 7-2 (1997)
CriteriaUBC 7-2 (1994)
CriteriaUL 10(b) (1997)
CriteriaNFPA 252 (1999)
CriteriaCAN4 S104 (1985)
CriteriaUL 10(b) 2008 (R2009)
CriteriaUL 10(c) (2009)
CriteriaCAN / ULC S104 (2015) (R2020)
CriteriaNFPA 252 (2017)
CSI Code08 11 00 Metal Doors and Frames
CSI Code08 11 13 Hollow Metal Doors and Frames
Fire Resistance20 Min w/Hose Stream PP Cat A Door
Fire Resistance45 Min Neutral Pressure
Fire Resistance60 Min PP Category A Door
Fire Resistance90 Min Neutral Pressure
Fire Resistance90 Min PP Category A Door
Fire Resistance45 Min PP Category A Door
Fire Resistance60 Min Neutral Pressure
Fire Resistance20 Min Neutral Pressure
Listing SectionCATEGORY A - DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Spec ID22571
SwingSingle Swing
SwingStandard Pairs
Temperature Rise@ 30 Min = 250° F MAX Where Lites Do Not Exceed 100 IN2
Temperature Rise@ 30 Min > 650° F
Design Documents
No Results
Public Documents