Steel-Faced (22, 24, 25 gauge) (Urethane Core Type) (Flush or Simulated Panel Type), Swinging Flush Door for installation in 1-1/2 hour locations. For use in listed (3-sided) 16 gauge welded or K.D. steel frames meeting ANSI-A155.1/UL-63 or General Product's adjustable frame or per framed manufacturer's listing(s).
Limitations*: Cylindrical latches with maximum 2-3/4" backset/Surface-Mounted Vertical Rod fire exit devices/Rim-Type fire exit devices/Deadbolts/Surface Bolts/Surface-Mounted Closers/Surface-Mounted Protection Plates/Surface-Mounted Door Bottoms/Temperature Rise - Greater than 650°F at 30 minutes.
Configuration |
Maximum Size* |
Single Swing |
3'0" wide x 7'0" high |
Standard Pairs |
NA |
Double Egress Pairs |
NA |
*See manufacturer's installation instructions for additional information on Smoke and Draft Control, size restrictions and limitations.
Testing Standards: UBC-7-2-97, UL-10C (Positive Pressure).