Intertek Directory of Building Products

VT 45 and 60 Minute Mineral Core Fire Doors Company: VT Industries, Inc.

Mineral Core Type, Swinging flush door for installation in up to 45 minute locations. For use in listed (3-sided) 16 gauge welded steel frames meeting ANSI-A155.1/UL-63 or as per the frame manufacturer's listing(s).

Limitations*

Mortise or Cylindrical Latches with maximum 5" Backset/Mortise Type Exit Device/Surface-Mounted Vertical Rod Fire Exit Devices/Rim-Type Fire Exit Devices/Deadbolts/Surface Bolts/Automatic Flush Bolts/Surface-Mounted Closers/Surface-Mounted Protection Plates/Viewer/Surface-Mounted Door Bottoms/Metal Edge or Astragal Optional/Temperature Rise - 250°F at 30 minutes.

Maximum Size of Openings*

Single Swing - 4'0" wide x 8'0" high

Standard Pairs - 8'0" wide x 8'0" high

Double Egress Pairs - Not Allowed

 

Mineral Core Type, Swinging flush door for installation in up to 60 minute locations. For use in listed (3-sided) 16 gauge welded steel frames meeting ANSI-A155.1/UL-63 or as per frame manufacturer's listing(s).

Limitations*

Mortise or Cylindrical Latches with maximum 5" Backset/Mortise Type Exit Device/Surface-Mounted Vertical Rod Fire Exit Devices/Rim Type Fire Exit Devices/Deadbolts/Surface-Mounted Closers/Surface-Mounted Protection Plates/Viewer/Surface-Mounted Door Bottoms/Temperature Rise - 250°F at 30 minutes.

Maximum Size of Openings*

Single Swing - 4'0" wide x 8'0" high

Standard Pairs - Not Allowed

Double Egress Pairs - Not Allowed

*See manufacturer's installation instructions for additional information on Smoke and Draft Control, size restrictions, and limitations.

Testing Standards

UBC-7-2-97/UL-10C (Positive Pressure).

Evaluated to the following...

This category includes doors evaluated without an edge-sealing system between the door and frame. It also includes doors evaluated with a sealing system incorporated (concealed or visible) into the edge of the door by the licensed manufacturer or machining distributor.

Meeting edges of pairs may require an astragal or an edge-sealing system. Please refer to individual door listings.
These doors are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in the accordance with the frame manufacturer's individual listing.

All doors listed in Category A are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.

All doors in this category are identified by a label or marking bearing the wording, "Listed Fire Door", a time interval, a temperature rise rating, a serial number and the Warnock Hersey Certification Mark and "UBC-7-2-97/UL 10C".

Listing Report Return to Search
Attributes
CriteriaUL 10(c) (1998)
CriteriaUBC 7-2 (1997)
CriteriaUL 10(c) (2009)
CriteriaUL 10(c) (2009) (R2015)
CriteriaCAN / ULC S104 (2015) (R2020)
CSI Code08 10 00 Doors and Frames
Fire Resistance45 Min Neutral Pressure
Fire Resistance60 Min PP Category A Door
Fire Resistance45 Min PP Category A Door
Fire Resistance60 Min Neutral Pressure
Listing SectionCATEGORY A - DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Spec ID22646
SwingSingle Swing
SwingStandard Pairs
Design Documents
No Results
Public Documents