Wood Core Type (Particle Board or Wood Block), Swinging Flush Design Fire Door for installation singly, including singles with Transom Panels, or in pairs, including Double Egress, in 20 minute locations.
Limitations
Unit, Mortise or Cylindrical Latches with up to a 5" backset/Surface Mounted Vertical Rod Fire Exit Hardware/Lights - 1,200 sq.in./Mortised or Surface Mounted Top and Bottom Bolts/Metal Edges required on pairs and double egress.
Maximum Size of Opening
Singles - 3'0" wide x 9'0" high or 4'0" wide x 8'0" high
Pairs - 8'0" wide x 8'0" high
Double Egress - 8'0" wide x 8'0" high
Door-Transom Assemblies - 3'0" wide x 9'0" high for a 3'0" wide x 6'0" high single door and a 3'0" wide x 3'0" high transom panel
Testing Standards: Tested per BOCA Basic/National, SBC, UBC requirements.
Note: For additional information please refer to the Marshfield listing.
Evaluated to the following...
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
CAN4-S104(ULC-S104), Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods for Fire Tests of Door Assemblies
UBC-7-2-94, Uniform Building Code
UL-10(b), Fire Tests of Door Assemblies
and are installed in accordance with the following:
NFPA-80, Fire Doors and Windows
Manufacturer's Instructions.
All assemblies are identified by a label or marking bearing the wording, "Listed (Product)", a time interval, temperature rise (if applicable), a serial number and the WHI Certification Mark.
(Unless otherwise specified, all Fire Doors have a nominal thickness of 1-3/4".)