Panel Type (Proprietary Construction), Fire Door for installation singly or in pairs in 20 minute locations.
Limitations: Unit, Mortise or Cylindrical Latches with up to a 2-3/4" backset/ Deadbolts/Mortised or Surface Mounted Rim Type Fire Exit Hardware/Metal Edges required on pairs.
| Maximum Size of Openings: |
Singles - 3'6" wide x 8'0" high
Pairs - 7'0" wide x 8'0" high |
Testing Standards: Tested per BOCA Basic/National, SBC, UBC requirements.
Evaluated to the following:
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
ASTM-E152, Methods of Fire Tests of Door Assemblies
CSFM-43.7, Methods of Fire Tests of Door Assemblies
CAN/ULC-S104, Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods for Fire Tests of Door Assemblies
UBC-7-2-94, Uniform Building Code
UL-10(b), Fire Tests of Door Assemblies
and are installed in accordance with the following:
NFPA-80, Fire Doors and Windows
Manufacturer's Instructions.
All assemblies are identified by a label or marking bearing the wording, "Listed (Product)", a time interval, temperature rise (if applicable), a serial number and the WHI Certification Mark.
(Unless otherwise specified, all Fire Doors have a nominal thickness of 1-3/4".)