Intertek Directory of Building Products

Pottorff Co Damper CFD-20, CFD-20ES Company: Pottorff

Ceiling Damper for Horizontal Installation in Air Duct Outlets of Restrained or Unrestrained Floor-Ceiling and Roof-Ceiling Assemblies with Fire Rating up to 3-Hours.

 

 

Model Nos.

Shape

Max. Area

(sq.in)

Max. Width

Max. Len.

Max. Dia.

Min. Width

Min. Len.

Min. Dia.

CFD-20
CFD-20ES

Square or Rectangular

576

24"

24"

NA

5"

5"

NA

 

 

 

**Listing for dampers only, and damper may be used with UL-listed exhaust fans manufactured by Broan.

Note:

1. All dimensions have a tolerance of ± 1/16".
2. The fire rating of the floor/ceiling or roof/ceiling assembly (in which a given damper is installed) determines the overall fire rating. Thus, a 3-hour fire rated damper installed in a 1-hour fire rated (wood truss type, combustible floor/ceiling) assembly results in an overall fire rating of 1-hour for the whole unit.
3. The total number of damper shall not exceed the total number of 12" diameter or larger duct openings in any individual floor/ceiling or roof/ceiling design.
4. The installation must be per manufacturer's installation instructions or NFPA-90A.
5. Abbreviations: CFD = Ceiling Fire Damper; ES = Extended Sleeve; NS = No Sleeve; R = Round; LP = Low Profile; SB = Single Blade; ESC2 = Extended Sleeve with Side Collar; SC2 = Side Collar; ESR = Extended Sleeve with Round Collar Duct Connection; EST = Extended Sleeve Tapered; STC 2 = Extended Sleeve Tapered with Side Collar; NSB = No Sleeve with "B" type duct connection; ESET = Extended Sleeve with Extra Transion

 

Evaluated to the following...
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
UL-555, Fire Dampers & Ceiling Dampers
ULC-S112(CAN-S112), Standard Method of Fire Test of Fire Damper Assemblies;
and are installed in accordance with the following:
NFPA-90A, Installation of Air Conditioning & Ventilating Systems.
Manufacturer's Instructions.
All assemblies are identified by all label bearing the wording, "Listed (Product)", a time interval, a serial number and the Warnock Hersey Certification Mark

Listing Report Return to Search
Attributes
CriteriaASTM E119 (2005a)
CriteriaASTM E119 (2010)
CSI Code23 00 00 Heating, Ventilating, and Air Conditioning (HVAC)
CSI Code23 33 00 Air Duct Accessories
Fire Resistance3 Hour Fire Rated
Listing SectionDAMPERS
Spec ID23338