Ruskin Ceiling Fire Dampers Model: CFD-4 Company: Ruskin Company

Ceiling Damper for horizontal mounting in air duct outlets in 3 hour non-combustible and 1 hour combustible ceiling locations.

 
Construction and Size Limitations shall be as follows:
 
SIZE LIMITATIONS, INCHES
Damper Type
Damper Shape
Protection On Back Of Damper Blades
Max Area
+, In
2
Max Width
Max Length
Min Width
Min Length
CFD-4* Square or Rectangular Wallboard & Ceramic Paper 576 24 24 4 10
CFD-4A* Square or Rectangular Wallboard & Ceramic Paper 576 24 24 4 10
CFD-4W Square or Rectangular Wallboard & Ceramic Paper 578 24 24 4 10
CFD-4AW Square or Rectangular Wallboard & Ceramic Paper 578 24 24 4 10

Ceiling Damper for horizontal mounting in air duct outlets in 3

Evaluated to the following:

Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
UL-555, Fire Dampers & Ceiling Dampers
CAN/ULC-S112, Standard Method of Fire Test of Fire Damper Assemblies;
and are installed in accordance with the following:
NFPA-90A, Installation of Air Conditioning & Ventilating Systems.
Manufacturer's Instructions.
All assemblies are identified by all label bearing the wording, "Listed (Product)", a time interval, a serial number and the Warnock Hersey Certification Mark.

Listing Report Return to Search
Attributes
CriteriaUL 555 (2006)
CriteriaCAN / ULC S112-M90 (1990)
CriteriaUL 555 (Feb 2010)
CriteriaUL 555C Rev 3 (May 2010)
CSI Code23 33 00 Air Duct Accessories
Listing SectionDAMPERS
Spec ID23560