Intertek Directory of Building Products

Chem-Pruf 45 Min Composite Core Fire Door NP Company: Chem-Pruf Door Company

Wood Core Type (Particle Board) (Fiberglass Reinforced Plastic-Faced), Swinging Flush Design Fire Door for installation singly or in pairs in 45 minute locations.
Limitations:
Unit, Mortise/Cylindrical Latches with a maximum of 2-3/4" Backset/Surface Mounted/Mortised Manual Top and Bottom (Flush) Bolts/Lights - 667 sq.in./Metal Edges with astragal required.


Maximum Size of Openings: Singles - 50-1/4" wide x 96" high
Pairs - 100-1/2" wide x 96" high
Maximum Clear View Opening Louvers - 10-5/8" wide x 16-5/8" high or 176.64 sq.in.

 

Evaluated to the following:

Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
ASTM-E152, Methods of Fire Tests of Door Assemblies
CSFM-43.7, Methods of Fire Tests of Door Assemblies
CAN4-S104(ULC-S104), Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods for Fire Tests of Door Assemblies
UBC-7-2-94, Uniform Building Code
UL-10(b), Fire Tests of Door Assemblies
and are installed in accordance with the following:
NFPA-80, Fire Doors and Windows

Manufacturer's Instructions.
All assemblies are identified by a label or marking bearing the wording, "Listed (Product)", a time interval, temperature rise (if applicable), a serial number and the WHI Certification Mark.
(Unless otherwise specified, all Fire Doors have a nominal thickness of 1-3/4".)

Listing Report Return to Search
Attributes
CriteriaNFPA 252 (1995)
CriteriaASTM E152-81a
CriteriaUBC 7-2 (1994)
CriteriaUL 10(b) (1997)
CriteriaCAN / ULC S104 (1980) (R1985)
CriteriaUL 10(b) 2008 (R2009)
CriteriaCAN / ULC S104 (2010)
CSI Code08 10 00 Doors and Frames
Fire Resistance45 Min Neutral Pressure
Fire Resistance20 Min Neutral Pressure
Listing SectionDOORS
Spec ID24959
SwingSingle Swing
SwingStandard Pairs
Design Documents
No Results
Public Documents
No Results