FIRE RESISTANT PRODUCTS & COMPONENTS
CATEGORY A DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
PRODUCT COVERED
Door Components, Inc 90 Minute Fire Door and Frame Assembly
PRODUCT DESCRIPTION
Hardware Limitations: Cylindrical / Cylindrical with Deadbolt / Mortise / Surface-Mounted Vertical Rod Fire Exit Devices / Rim-Type Surface Mounted Fire Exit Devices / Surface Bolts or Mortised Flush Bolts Listed flush or surface bolts, automatic, manual, or self-latching types, 3/4” minimum throw/ Surface Mounted or Concealed Door Bottoms / Surface Mounted Closer or Overhead Stops / Viewer / Vision Kit - Max. 100 sq. in. / Raceway / EPT/ 16" Protection Plates . 1-1/2" Astragal required on pairs. Hinges per NFPA 80, 5 hinges per leaf over 10’ door height. Active leaf of pairs exceeding 8’ width – Head of active leaf at lock stile prepared for listed, mortise type, auxiliary fire latch, engaging into frame head rabbet preparation.
Configuration Maximum Size
Single 5'0" wide x 12'0" high
Standard Pair 10'0" wide x 12'0" high
Double Egress Not Allowed
Minimum thickness: 1-3/4"
Maximum Thickness; 2-1/4"
For 3-point latched pairs, the active leaf requires a standard latch with a minimum 3/4" throw.
The product noted above has been tested and qualified per UL 10B, UL 10C, NFPA 252, and CAN / ULC S104 for a 90 Minute Positive Pressure Fire Rating.
These doors are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in the accordance with the frame manufacturer's individual listing.
The door noted above is eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.