Door Components 90 Min. Hollow Metal Door & Frame Assembly Company: DCI Hollow Metal

FIRE RESISTANT PRODUCTS & COMPONENTS

CATEGORY A DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED

PRODUCT COVERED
Door Components, Inc  90 Minute Fire Door and Frame Assembly

PRODUCT DESCRIPTION
Hardware Limitations:   Cylindrical / Cylindrical with Deadbolt / Mortise / Surface-Mounted Vertical Rod Fire Exit Devices / Rim-Type Surface Mounted Fire Exit Devices / Surface Bolts or Mortised Flush Bolts Listed flush or surface bolts, automatic, manual, or self-latching types, 3/4” minimum throw/ Surface Mounted or Concealed Door Bottoms / Surface Mounted Closer or Overhead Stops / Viewer / Vision Kit - Max. 100 sq. in. / Raceway / EPT/ 16" Protection Plates . 1-1/2" Astragal required on pairs. Hinges per NFPA 80, 5 hinges per leaf over 10’ door height.  Active leaf of pairs exceeding 8’ width – Head of active leaf at lock stile prepared for listed, mortise type,  auxiliary fire latch, engaging into frame head rabbet preparation.

Configuration                   Maximum Size
Single                          5'0" wide x 12'0" high

Standard Pair            10'0" wide x 12'0" high                                  

Double Egress                 Not Allowed

Minimum  thickness:         1-3/4"
Maximum Thickness;        2-1/4"
 
For 3-point latched pairs, the active leaf requires a standard latch with a minimum 3/4" throw.

The product noted above has been tested and qualified per UL 10B, UL 10C, NFPA 252, and CAN / ULC S104 for a 90 Minute Positive Pressure Fire Rating.  

These doors are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in the accordance with the frame manufacturer's individual listing.

The door noted above is eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.
Listing Report Return to Search
Attributes
CriteriaUL 10(c) (2009)
CriteriaCAN / ULC S104 (2010)
CriteriaCAN / ULC S104 (2015) (R2020)
CriteriaUL 10(b) (2008) (R2020)
CriteriaUL 10(c) (2016) Ed. 3 (R:27 May 2021)
CriteriaNFPA 252 (2022)
CSI Code08 11 00 Metal Doors and Frames
CSI Code08 11 13 Hollow Metal Doors and Frames
Fire Resistance90 Min Positive Pressure
Frame OptionsHollow Metal
Listing SectionDOORS
Spec ID25016
SwingSingle Swing
SwingStandard Pairs
Temperature Rise@ 30 Min = 450° F MAX Where Lites Do Not Exceed 100 IN2