Door Components 90-180 Min. Insulated, Rib-Stiffened, Metal Doors Company: DCI Hollow Metal

Product Covered
90 Minute to 3-Hour Hollow Metal Doors
 
Product Description
Hollow Metal Type (minimum 18 gauge) (Steel-Faced) (Vertically-Stiffened), Swinging Flush Design Fire Door for installation singly or in pairs, including double egress, in up to 3 hour locations, for installation in masonry openings
 
Maximum Sizes – 90 Minute Doors:
Single-Swing 4'-0" x 10'-0"
Dutch Door (single) 4'0" x 8'-0"
Pairs 8'-0" x 10'-0"
Double Egress 6'-10" x 10'-0"
Minimum thickness:        1-3/4" 
Maximum thickness:       2-1/4"
 
Maximum Sizes – 3 Hour Doors:
Single-Swing 4'-0" x 9'-0"
Dutch Door (single) 4'0" x 8'-0"
Pairs 8'-0" x 9'-0"
Double Egress 8'-0" x 10'-0"*
Minimum thickness:        1-3/4" 
Maximum thickness:       2-1/4"
 *Requires 4 pt latching and astragal for heights over 8'0"
Limitations: Mortise or Cylindrical Latches/Surface Mounted Vertical Rod Fire Exit Hardware/Surface Mounted Rim Type Fire Exit Hardware/Mortised or Surface Mounted Top and Bottom Bolts.  Astragal required for double egress doors.  Maximum 100 in2 lights for 90 minute doors.  Lead lining within core permitted. 
 
Evaluated to the Following
This category includes doors evaluated without an edge-sealing system between the door and frame. It also includes doors evaluated with a sealing system incorporated (concealed or visible) into the edge of the door by the licensed manufacturer or machining distributor.
Meeting edges of pairs may require an astragal or an edge-sealing system. Please refer to individual door listings.
These doors are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in the accordance with the frame manufacturer's individual listing.
All doors listed in Category A are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.
All doors in this category are identified by a label or marking bearing the wording, "Listed Fire Door", a time interval, a temperature rise rating, a serial number, and the Warnock Hersey Certification Mark. See Positive Pressure Section Header for more information.
Listing Report Return to Search
Attributes
CriteriaUL 10(b) 2008 (R2009)
CriteriaUL 10(c) (2009)
CriteriaCAN / ULC S104 (2010)
CriteriaNFPA 252 (2012)
CriteriaCAN / ULC S104 (2015) (R2020)
CriteriaUL 10(c) (2016) Ed. 3 (R:27 May 2021)
CriteriaNFPA 252 (2022)
CSI Code08 11 00 Metal Doors and Frames
Fire Resistance3 Hour PP Category A Door
Fire Resistance90 Min Positive Pressure
Listing SectionDOORS
Spec ID25017
SwingSingle Swing
SwingStandard Pairs
SwingDouble Egress