Composite Core Type, Swinging Flush Design Fire Door for installation as Single, Pairs, Double Egress, or with Transom, in 45 minute locations.
Limitations: Unit (Preassembled), Mortise or Cylindrical Latches with up to a 5" backset / Deadbolts / Single Point Latches / Mortised or Surface Mounted Rim Type Fire Exit Hardware / Surface Mounted Vertical Rod Fire Exit Hardware / Protective Plates up to 48" / Lites - up to 1296 sq.in. / Viewers / Mortised or Surface Mounted Automatic or Manual Top and Bottom (Flush) Bolts / Mortised Automatic Door Bottoms / Louver - up to 24" x 24" / Plant-Ons - Applied Mouldings / Electric Raceways / Surface Mounted Closers.
45 Minute Configuration |
Maximum Size of Openings |
Single Swing |
4'0" wide x 10'0" high or 3'0" wide x 10'0" high |
Pairs Regular Swing |
8'0" wide x 9'0" high Metal Edges and Astragal required
8'0" wide x 8'0" high Surface Vertical Rod and Metal Edges required |
Double Egress |
8'0" wide x 8'0" high Metal Edges and Astral required |
Door and Transom (Single Swing Only) |
3'0" wide x 9'0" high Max Transom 3'0" wide x 3'4" high |
Composite Core Type, Swinging Flush Design Fire Door for installation as Single, Pairs, Double Egress, or with Transom, in 60 minute locations.
Limitations: Unit (Preassembled), Mortise or Cylindrical Latches with up to a 5" backset / Deadbolts / Mortised or Surface Mounted Rim Type Fire Exit Hardware / Surface Mounted Vertical Rod Fire Exit Hardware / Protective Plates up to 48" / Surface Mounted Closers / Lites - up to 100 sq.in. / Viewers / Mortised or Surface Mounted Automatic or Manual Top and Bottom (Flush) Bolts / Louvers - up to 24" x 24" / Plant-Ons - Applied Mouldings / Electric Raceways / Single Point Latches.
60 Minute Configuration |
Maximum Size of Openings |
Single Swing |
4'0" wide x 10'0" high or 3'0" wide x 10'0" high |
Pairs Regular Swing |
8'0" wide x 8'0" high Metal Edges and Astragal required
8'0" wide x 8'0" high Surface Vertical Rod and Metal Edges required |
Double Egress |
8'0" wide x 8'0" high Metal Edges and Astral required |
Door and Transom (Single Swing Only) |
3'0" wide x 9'0" high Max Transom 3'0" wide x 3'4" high |
Composite Core Type, Swinging Flush Design Fire Door for installation as Single, Pairs, or Double Egress, in 90 minute locations.
Limitations: Unit (Preassembled), Mortise or Cylindrical Latches with up to a 5" backset / Deadbolts / Mortised or Surface Mounted Rim Type Fire Exit Hardware / Surface Mounted Vertical Rod Fire Exit Hardware / Protective Plates up to 48" / Surface Mounted Closers / Lites - up to 100 sq.in. / Viewers / Mortised or Surface Mounted Automatic or Manual Top and Bottom (Flush) Bolts / Louvers - up to 24" x 24" / Plant-Ons - Applied Mouldings / Electric Raceways / Single Point Latches.
90 Minute Configuration |
Maximum Size of Openings |
Single Swing |
4'0" wide x 9'0" high |
Pairs Regular Swing |
6'0" wide x 7'0" high Metal Edges and Astragal required
8'0" wide x 8'0" high Surface Vertical Rod and Metal Edges required |
Double Egress |
N/A |
Door and Transom |
3'0" wide x 9'0" high Max Transom 3'0" wide x 3'4" high |
NOTE: For additional information please refer to the Weyerhaeuser - SLM listing, and the Georgia Pacific Corp. listing.
Evaluated to the following:
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
ASTM-E152, Methods of Fire Tests of Door Assemblies
CSFM-43.7, Methods of Fire Tests of Door Assemblies
CAN4-S104(ULC-S104), Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods for Fire Tests of Door Assemblies
UBC-7-2-94, Uniform Building Code
UL-10(b), Fire Tests of Door Assemblies
and are installed in accordance with the following:
NFPA-80, Fire Doors and Windows
Manufacturer's Instructions.
All assemblies are identified by a label or marking bearing the wording, "Listed (Product)", a time interval, temperature rise (if applicable), a serial number and the WHI Certification Mark.