Eggers 45-90 Min Composite Core Fire Doors Company: Eggers Division, LLC

Composite Core Type, Swinging Flush Design Fire Door for installation as Single, Pairs, Double Egress, or with Transom, in 45 minute locations. 

Limitations: Unit (Preassembled), Mortise or Cylindrical Latches with up to a 5" backset / Deadbolts / Single Point Latches / Mortised or Surface Mounted Rim Type Fire Exit Hardware / Surface Mounted Vertical Rod Fire Exit Hardware / Protective Plates up to 48" / Lites - up to 1296 sq.in. / Viewers / Mortised or Surface Mounted Automatic or Manual Top and Bottom (Flush) Bolts / Mortised Automatic Door Bottoms / Louver - up to 24" x 24" / Plant-Ons - Applied Mouldings / Electric Raceways / Surface Mounted Closers. 

45 Minute Configuration

Maximum Size of Openings

Single Swing

4'0" wide x 10'0" high or
3'0" wide x 10'0" high

Pairs Regular Swing

8'0" wide x 9'0" high
Metal Edges and Astragal required

8'0" wide x 8'0" high
Surface Vertical Rod and Metal Edges required

Double Egress

8'0" wide x 8'0" high
Metal Edges and Astral required

Door and Transom (Single Swing Only)

3'0" wide x 9'0" high
Max Transom 3'0" wide x 3'4" high

   

Composite Core Type, Swinging Flush Design Fire Door for installation as Single, Pairs, Double Egress, or with Transom, in 60 minute locations. 

Limitations: Unit (Preassembled), Mortise or Cylindrical Latches with up to a 5" backset / Deadbolts / Mortised or Surface Mounted Rim Type Fire Exit Hardware / Surface Mounted Vertical Rod Fire Exit Hardware / Protective Plates up to 48" / Surface Mounted Closers / Lites - up to 100 sq.in. / Viewers / Mortised or Surface Mounted Automatic or Manual Top and Bottom (Flush) Bolts / Louvers - up to 24" x 24" / Plant-Ons - Applied Mouldings / Electric Raceways / Single Point Latches.  

60 Minute Configuration

Maximum Size of Openings

Single Swing

4'0" wide x 10'0" high or
3'0" wide x 10'0" high

Pairs Regular Swing

8'0" wide x 8'0" high
Metal Edges and Astragal required

8'0" wide x 8'0" high
Surface Vertical Rod and Metal Edges required

Double Egress

8'0" wide x 8'0" high
Metal Edges and Astral required

Door and Transom (Single Swing Only)

3'0" wide x 9'0" high
Max Transom 3'0" wide x 3'4" high

 

 

Composite Core Type, Swinging Flush Design Fire Door for installation as Single, Pairs, or Double Egress, in 90 minute locations. 

Limitations: Unit (Preassembled), Mortise or Cylindrical Latches with up to a 5" backset / Deadbolts / Mortised or Surface Mounted Rim Type Fire Exit Hardware / Surface Mounted Vertical Rod Fire Exit Hardware / Protective Plates up to 48" / Surface Mounted Closers / Lites - up to 100 sq.in. / Viewers / Mortised or Surface Mounted Automatic or Manual Top and Bottom (Flush) Bolts / Louvers - up to 24" x 24" / Plant-Ons - Applied Mouldings / Electric Raceways / Single Point Latches.  

90 Minute Configuration

Maximum Size of Openings

Single Swing

4'0" wide x 9'0" high

Pairs Regular Swing

6'0" wide x 7'0" high
Metal Edges and Astragal required

8'0" wide x 8'0" high
Surface Vertical Rod and Metal Edges required

Double Egress

N/A

Door and Transom

3'0" wide x 9'0" high
Max Transom 3'0" wide x 3'4" high

 

 NOTE: For additional information please refer to the Weyerhaeuser - SLM listing, and the Georgia Pacific Corp. listing.

Evaluated to the following:

Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:

ASTM-E152, Methods of Fire Tests of Door Assemblies
CSFM-43.7, Methods of Fire Tests of Door Assemblies
CAN4-S104(ULC-S104), Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods for Fire Tests of Door Assemblies
UBC-7-2-94, Uniform Building Code
UL-10(b), Fire Tests of Door Assemblies

and are installed in accordance with the following:

NFPA-80, Fire Doors and Windows
Manufacturer's Instructions.

All assemblies are identified by a label or marking bearing the wording, "Listed (Product)", a time interval, temperature rise (if applicable), a serial number and the WHI Certification Mark.
(Unless otherwise specified, all Fire Doors have a nominal thickness of 1-3/4".)

 

Listing Report Return to Search
Attributes
CriteriaNFPA 80 (1999)
CriteriaNFPA 252 (1995)
CriteriaASTM E152-81a
CriteriaCSFM 43.7
CriteriaUBC 7-2 (1994)
CriteriaUL 10(b) (1997)
CriteriaCAN4 S104 (1985)
CriteriaUL 10(b) 2008 (R2009)
CriteriaCAN / ULC S104 (2010)
CSI Code08 10 00 Doors and Frames
CSI Code08 14 00 Wood Doors
Fire Resistance45 Min Neutral Pressure
Fire Resistance90 Min Neutral Pressure
Fire Resistance60 Min Neutral Pressure
Listing SectionDOORS
Spec ID25064
SwingSingle Swing
SwingStandard Pairs
SwingDouble Egress
Design Documents
No Results
Public Documents
No Results