Intertek Directory of Building Products

Titan Steel Door, LLC - 3 Hour Metal Detention Fire Doors NP Company: Titan Steel Door, LLC

PRODUCT DESCRIPTION

Swing Type Fire Door (12, 14 gauge)(Steel-Faced)(Vertically Steel-Stiffened) for installation in up to 3 hour, neutral pressure, masonry wall locations.

20 and 45 Minute Doors

 

Swing Maximum Size of Openings Glass Lights
Single 4'0" wide x 8'0" high Max 100 sq.in. for listed wire glass; Max 1302 sq.in. for listed ceramic glass*
Pairs 6'0" wide x 8'0" high Max 100 sq.in. for listed wire glass; Max 1302 sq.in. for listed ceramic glass*

 

*NOTE: Maximum 1302 sq.in. applies to Pyran Platinum ceramic glazing and any listed ceramic glazing approved for a maximum area of equal or greater. Maximum area limited by the listed glazing specifications in all other cases.

Limitations: Active Leaf-Single Point Latches (Mortise or Cylindrical) or Fire Exit Hardware/Inactive Leaf-Top and bottom Automatic or Manual Flush Bolt/Astragal/Surface Mounted Vertical Rod fire Exit Device for Active-Active Leaf.

60 to 90 Minute Doors

 

Swing Maximum Size of Openings Glass Lights
Single 4'0" wide x 8'0" high Maximum 100 sq.in.

 

Limitations: Mortise, Cylindrical Latch, or Fire Exit Hardware.

180 Minute Doors

 

Swing Maximum Size of Openings Glass Lights
Single 4'0" wide x 8'0" high Not Allowed

 

Evaluated to the following:

Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
ASTM-E152, Methods of Fire Tests of Door Assemblies
CAN/ULC-S104, Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods for Fire Tests of Door Assemblies
UBC-7-2-94, Uniform Building Code
UL-10(b), Fire Tests of Door Assemblies
and are installed in accordance with the following:
NFPA-80, Fire Doors and Windows

Manufacturer's Instructions.
All assemblies are identified by a label or marking bearing the wording, "Listed (Product)", a time interval, temperature rise (if applicable), a serial number and the WHI Certification Mark.

Doors are eligible to bear the “S” (for Smoke & Draft Control assemblies) if a listed “Category H - Smoke & Draft Control Gasket” has been applied to the assembly. Please refer to Category H for individual gasket manufacturer’s listings.

Listing Report Return to Search
Attributes
CriteriaUBC 7-2 (1994)
CriteriaUL 10(b) (1997)
CriteriaCAN / ULC S104 (1980) (R1985)
CriteriaNFPA 252 (2008)
CriteriaUL 10(b) 2008 (R2009)
CriteriaCAN / ULC S104 (2010)
CriteriaNFPA 252 (2012)
CriteriaUL 10(b) (2008) (R2015)
CSI Code08 11 00 Metal Doors and Frames
Fire Resistance45 Min Neutral Pressure
Fire Resistance90 Min Neutral Pressure
Fire Resistance3 Hour Neutral Pressure
Fire Resistance60 Min Neutral Pressure
Fire Resistance20 Min Neutral Pressure
Listing SectionDOORS
Spec ID25255
SwingSingle Swing
SwingStandard Pairs
Design Documents
No Results
Public Documents