PRODUCT DESCRIPTION
Swing Type Fire Door (12, 14 gauge)(Steel-Faced)(Vertically Steel-Stiffened) for installation in up to 3 hour, neutral pressure, masonry wall locations.
20 and 45 Minute Doors
Swing |
Maximum Size of Openings |
Glass Lights |
Single |
4'0" wide x 8'0" high |
Max 100 sq.in. for listed wire glass; Max 1302 sq.in. for listed ceramic glass* |
Pairs |
6'0" wide x 8'0" high |
Max 100 sq.in. for listed wire glass; Max 1302 sq.in. for listed ceramic glass* |
*NOTE: Maximum 1302 sq.in. applies to Pyran Platinum ceramic glazing and any listed ceramic glazing approved for a maximum area of equal or greater. Maximum area limited by the listed glazing specifications in all other cases.
Limitations: Active Leaf-Single Point Latches (Mortise or Cylindrical) or Fire Exit Hardware/Inactive Leaf-Top and bottom Automatic or Manual Flush Bolt/Astragal/Surface Mounted Vertical Rod fire Exit Device for Active-Active Leaf.
60 to 90 Minute Doors
Swing |
Maximum Size of Openings |
Glass Lights |
Single |
4'0" wide x 8'0" high |
Maximum 100 sq.in. |
Limitations: Mortise, Cylindrical Latch, or Fire Exit Hardware.
180 Minute Doors
Swing |
Maximum Size of Openings |
Glass Lights |
Single |
4'0" wide x 8'0" high |
Not Allowed |
Evaluated to the following:
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
ASTM-E152, Methods of Fire Tests of Door Assemblies
CAN/ULC-S104, Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods for Fire Tests of Door Assemblies
UBC-7-2-94, Uniform Building Code
UL-10(b), Fire Tests of Door Assemblies
and are installed in accordance with the following:
NFPA-80, Fire Doors and Windows
Manufacturer's Instructions.
All assemblies are identified by a label or marking bearing the wording, "Listed (Product)", a time interval, temperature rise (if applicable), a serial number and the WHI Certification Mark.
Doors are eligible to bear the “S” (for Smoke & Draft Control assemblies) if a listed “Category H - Smoke & Draft Control Gasket” has been applied to the assembly. Please refer to Category H for individual gasket manufacturer’s listings.