Pressed Steel Door Frame (16, 14 gauge) (Welded Up) with Side Panels or Side Lights and Transom Panels or Transom Lights for installation in 1-1/2 hour locations in steel/wood stud drywall or masonry openings.
Note: Lights limit locations to 3/4 hour maximum, Solid Panels must be used in locations exceeding 3/4 hour.
| Maximum Overall Dimensions: |
144" wide x 144" high |
| Minimum Throat Openings: |
Masonry Walls - 3-3/4"; Drywall - 3-5/8" |
Evaluated to the following:
Unless otherwise noted, assemblies in this section have been tested to the following standards:
UL-10(c), Standard for Positve Pressure Fire Tests of Door Assemblies;
CAN/ULC-S104, Standard Method for Fire Tests of Door Assemblies;
NFPA-252, Standard Methods of Fire Tests of Door Assemblies;
UL-10(b), Fire Tests of Door Assemblies;
and are installed, unless otherwise noted, in accordance with the following:
NFPA-80, Fire Doors & Windows.
Manufacturer's Instructions.
Listed maximum sizes of lights are based on sizes tested and may exceed local code requirements.
All frames are identified by either a label or embossed marking bearing the wording "Listed (Product)" and the WHI Certification Mark. Frames rated for less than 3 hours also bear the time interval. Frame labels that do not include a time interval are rated for 3 hours.