Premier Products 3 Hour Honeycomb Core Steel Fire Door
Company: Premier Steel Doors and Frames, Inc.
Hollow Metal Type (16/18 gauge) (Steel-Faced) (Paper Honeycomb Core), Swinging Flush Design Fire Door for installation singly in 3 hour locations.
Limitations: Unit, Mortise or Cylindrical Latches with up to a 5" backset/Mortised or Surface Mounted Vertical Rod Fire Exit Hardware/Surface Mounted Rim Type Fire Exit Hardware/
| Maximum Size of Openings: |
Singles - 4'0" wide x 8'0" high
or 3'6" wide by 9'0" high
Pairs - Not Allowed
Double Egress - Not Allowed |
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
Ul 10(c) Standard for Positve Pressure Fire Test of Door Assemblies
CAN/ULC-S104, Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods for Fire Tests of Door Assemblies
UL-10(b), Fire Tests of Door Assemblies
and are installed in accordance with the following:
NFPA-80, Fire Doors and Windows
Manufacturer's Instructions.
All assemblies are identified by a label or marking bearing the wording, "Listed (Product)", a time interval, temperature rise (if applicable), a serial number and the WHI Certification Mark.
(Unless otherwise specified, all Fire Doors have a nominal thickness of 1-3/4".)