Intertek Directory of Building Products

Rectorseal's Blazeseal Edge-Sealing System Company: RectorSeal, LLC

FIRE RESISTANT PRODUCTS & COMPONENTS

Product Description: 

Rectorseal's Blazeseal edge-sealing system for use in up to 90 minutes fire-rated assemblies around the perimeter of the door attached to frame/door.

Limitations: 

Two strips side by side and GP Construction required for 60-90 minute assemblies.

DOOR ASSEMBLIES

Rating

Maximum Assembly Size

Door Type

Frame Type

Hardware Limitations

20 min w/hose steam

UBC Standard 7-2-1997 Part I

4’0” x 9’0”

(Single Swing)

 

 8’0” x 9’0” (Standard Pair)

 

8’0” x 9’0”

(Double Egress Pair)

Any Category “B” door listed and labeled for 20 minute fire rating with hose stream

Any Category “C” door frame listed and labeled for 20 minute fire rating with hose stream

Pairs require 3-point or 4-point latching with surface-mounted hardware, cylindrical or mortise latches with minimum ¾” throw, automatic or manual flush bolts

45 minute

UBC Standard 7-2-1997 Part I

4’0” x 10’0”

(Single Swing)

 

 8’0” x 9’0” (Standard Pair)

 

8’0” x 8’0”

(Double Egress Pair)

Any Category “B” door listed and labeled for 45 minute fire rating

 

Single-swing or pairs above 8’0” or double egress pairs must be Marshfield DoorSystem mineral core doors

Any Category “C” door frame listed and labeled for 45 minute fire rating

 

Single-swing pairs above 8’0” or double egress pairs must be 16/18 gauge steel door frames

Pairs require 3-point or 4-point latching with surface-mounted hardware, cylindrical or mortise latches with minimum 3/4” throw, automatic or manual flush bolts

60 minute

UBC Standard 7-2-1997 Part I

4’0” x 10’0”

(Single Swing)

 

 8’0” x 9’0” (Standard Pair)

 

8’0” x 8’0”

(Double Egress Pair)

Any GP construction Category “B” door listed and labeled for 60 minute fire rating

 

Single-swing or pairs above 8’0” or double egress pairs must be Marshfield DoorSystem mineral core doors

Any Category “C” door frame listed and labeled for 60 minute fire rating

 

Single-swing pairs above 8’0” or double egress pairs must be 16/18 gauge steel door frames

For GP mineral core doors: two strips side by side must be used

 

Pairs require 3-point or 4-point latching with surface-mounted hardware, cylindrical or mortise latches with minimum 3/4” throw, automatic or manual flush bolts

90 minute

UBC Standard 7-2-1997 Part I

4’0” x 10’0”

(Single Swing)

 

 8’0” x 9’0” (Standard Pair)

 

8’0” x 8’0”

(Double Egress Pair)

Any GP construction Category “B” door listed and labeled for 90 minute fire rating

 

Single-swing or pairs above 8’0” or double egress pairs must be Marshfield DoorSystem mineral core doors

Any Category “C” door frame listed and labeled for 90 minute fire rating

 

Single-swing pairs above 8’0” or double egress pairs must be 16/18 gauge steel door frames

For GP mineral core doors: two strips side by side must be used

 

Pairs require 3-point or 4-point latching with surface-mounted hardware, cylindrical or mortise latches with minimum 3/4” throw, automatic or manual flush bolts

Listing Report Return to Search
Attributes
CriteriaUL 10(c) (1998)
CriteriaUBC 7-2 (1997)
CriteriaCAN4 S104 (1985)
CriteriaUL 10(c) (2009)
CriteriaCAN / ULC S104 (2010)
CSI Code07 90 00 Joint Protection
Fire Resistance20 Min Category G Edge-Sealing Systems
Fire Resistance45 Min Category G Edge-Sealing Systems
Fire Resistance60 Min Category G Edge-Sealing Systems
Fire Resistance90 Min Category G Edge-Sealing Systems
Listing SectionCATEGORY G - EDGE-SEALING SYSTEMS
Spec ID25409
Design Documents