Intertek Directory of Building Products

Total Door Category D Door/Frame Assembly 20-180 Min Model Stl-180-Stif Company: Total Door II, Inc.

FIRE RESISTANT PRODUCTS & COMPONENTS 

 

Steel-Faced (16, 18, 20 gauge) (Stiffened Core Type), Swinging Flush Door installation in 3 hour locations. For use in listed proprietary (3-sided) 16 gauge welded steel frames or as per frame manufacturer's listing(s).
 

Limitations*: Proprietary Latches & Hinge System/Frame/Surface-Mounted Closers/Concealed Closer Arms/Surface-Mounted Protection Plates/Viewer/Surface-Mounted or Mortised Door Bottoms/Metal Edge or Astragal Not Required/Temperature Rise - Greater than 650°F at 30 minutes. 

 

Configuration

Maximum Size*

Single Swing

4'2-3/16" wide x 9'0" high

Standard Pairs

8'4-3/8" wide x 9'0" high

Double Egress Pairs

8'4-3/8" wide x 9'0" high

 
*See manufacturer's installation instructions for additional information on Smoke and Draft Control, size restrictions and limitations.

 The door and frame assembly noted above was tested in conjunction to test method UL 1784, "Standard for Air Leakage Tests of Door Assemblies."  For the air leakage compliance noted below, the assembly must have a fire rated surface applied or concealed W60 door sweep applied to the bottom of the door and a fire rated air foil W-12 seal applied to the stop of the frame head.  W-12 air foil seals are also factory applied to the inside of the door's locking channel. 
 
Standard / Code Section Description Results
UL 1784 Standard for Air Leakage Tests of Door Assemblies See Test Report for specific leakage values.
2009 IBC Section 711.5.2 and 2012 IBC Section 710.5.2.2 (Air Leakage Requirement) Max. air leakage: < 3 cfc per sq.ft. of opening at 0.1 in. of w.c. pressure differential at ambient temperature. Complies
2009 IBC Section 711.5.2 and 2012 IBC Section 710.5.2.2 (Air Leakage Requirement) Max. air leakage: < 3 cfc per sq.ft. of opening at 0.1 in. of w.c. pressure differential at 400 degrees F. Complies
Listing Report Return to Search
Attributes
CriteriaUBC 7-2 (1997)
CriteriaCAN4 S104 (1985)
CriteriaUL 10(c) (2009)
CriteriaUL 1784 (2009)
CriteriaCAN / ULC S104 (2010)
CriteriaCAN / ULC S104 (2015) (R2020)
CriteriaUL 10(c) (2016)
CSI Code08 10 00 Doors and Frames
Fire Resistance20 Min w/Hose Positive Pressure
Fire Resistance45 Min Positive Pressure
Fire Resistance90 Min Positive Pressure
Fire Resistance60 Min Positive Pressure
Fire Resistance3 Hour Positive Pressure
Listing SectionCATEGORY D - DOOR/FRAME ASSEMBLIES
Spec ID25497
Design Documents
No Results
Public Documents