Intertek Directory of Building Products

Adams Rite Fire Rated Exit Hardware Company: Adams Rite Manufacturing


ABBREVIATIONS USED IN CHART:
 
 
AL Aluminum
CVR Concealed vertical rod
CVR-TRO Concealed vertical rod, top rod only
HM Hollow metal or steel covered composite
RE Rim exit
SVR Surface vertical rod
SVR-TRO Surface vertical rod, top rod only
SPM Single point mortise
W Wood or plastic faced composite
 
 
 
FIRE EXIT HARDWARE
Model Type Rating Door Construction SIZE OVERSIZED
Maximum
Door
Singles
Pairs & Double Egress Singles
(90 Min)
Pairs & Double Egress
(90 MIN)
3100 SVR 3 HR HM  
 
4'-0" x 10'-0"
 
8'-0" x 10'-0" 4’-3” X 9’-0” 8’-6” X 9’-0”
3100 SVR 90 MIN W 4'-0" x 10'-0" 8’-0” x 9’-0” 4’-3” X 9’-0” 8’-6” X 9’-0”
3100T SVR-TRO 3 HR HM  
 
4'-0" x 8'-0"
 
 
 
8'-0" x 10'-0"
 
4’-3” X 9’-0” 8’-6” X 9’-0”
3100W SVR-TRO 1-1/2 HR W 4'-0" x 8'-0"
()
8'-0" x 8'-0"
(Std. Pairs & Double Egress)
N/A N/A
3100W SVR-TRO 20 MIN W 4’0” x 9’0” (Wood Door Only) 8’0” x 9’0” (Standard Pairs Only) N/A N/A
3300* SPM 3 HR HM 4'-0" x 10'-0" 8'-0" x 10'-0" (Active Leaf) N/A N/A
3375** SPM 3 HR HM 4'-0" x 10'-0" 8'-0" x 10'-0" (Active Leaf) N/A N/A
3900 CVR-TRO 1-1/2 HR W 4'-0" x 9'-0" 8'-0" x 9'-0" N/A N/A
3600 (+) CVR 3 HR HM N/A 8'-0" x 10'-0" 4’-03” X 9’-0” 8’-6” X 9’-0”
3676***(+) CVR-TRO 3 HR HM N/A 8'-0" x 10'-0" 4’-3” X 9’-0” 8’6” X 9’-0”
3600T (+) CVR-TRO 3 HR HM N/A 8'-0" x 10'-0", Std. Pairs: 8’0” x 10’0”; Double Egress (1-1/2 hour): 8’0” x 10’0” ; Double Egress (3 hour):  8’0” x 8’0” 4’-3” X 9’-0” 8’-6” X 9-’0”
3700**** (+) RE 3 HR HM - W 4'-0" x 10'-0" 8'-0" x 10'-0" N/A N/A
3940 CVR-TRO 20 MIN W 4’0” x 9’0” (Wood Door Only) 8’0” x 9’0” (Standard Pairs & Double Egress) N/A N/A
3976 (+) CVR-TRO 20 MIN W 4’0” x 9’0” (Wood Door Only) 8’0” x 9’0” (Standard Pairs & Double Egress) N/A N/A
3940 CVR-TRO 1-1/2 HR W 4’0” x 9’0” (Wood Door Only) 8’0” x 9’0” (Standard Pairs & Double Egress) N/A N/A
3976 (+)  CVR-TRO 1-1/2 HR W 4’0” x 9’0” (Wood Door Only) 8’0” x 9’0” (Standard Pairs & Double Egress) N/A N/A
EX88***** (+) RE 3 HR HM - W 4'-0" x 10'-0" 8'-0" x 10'-0" N/A N/A
*May be used with Model 3100 or 3600 with an open back strike. (steel door only)
**May be used with Model 3676, 3644, 3621 with an open back strike. (steel door only)
***May be used with Model 3621.
****May be used with Model 3889 mullion for doors in pairs.
*****May be used with Model M88F mullion for doors in pairs.

(+) May be suffixed CA in reference to UL Certifications Directory Number FVSR.SA5757 in which California Building Code (2013) Sec. 11B-309.4 compliance was achieved (Intertek Listing is for fire resistance only).  
 
 
NOTES
  1. May be used with suffix "A" to indicate on board alarm system, "M" for Monitor Switch, "EL" for Electric Latch Retraction , "ED & EDM" for Electric Dogging, "CA" for California Compliant Model.
  2. These devices may be used with the 3000 series entry functions.
  3. Single hollow metal doors using vertical rod exit device must use a heat activated locking pin 12” from the floor in the lead edge of the door.
  4. Doors using Model 3900 CVR-TRO must be provided with heat activated locking pins as follows: (A) In the lower side of the door at the latch corner for ALL single doors (45, 60 & 90 minute rated) and for standard & double egress pairs (45 minute rated) and (B) In the bottom of the door at the bottom latch corner on both leaves for standard & double egress pairs (60 & 90 minute rated).  Exception: No pins required in 20 minute without hose stream.
  5. Doors using Model 3900 CVR-TRO must have stiles made from Georgia Pacific Firestop material or Warm Springs Tectonite in accordance with their respective procedures.
  6. 3644 & 3645 Lever X Lever Set (Top Latch only) for use in (standard or double egress pairs only) Steel Doors for up to 3 hour locations.
  7. Doors using Models 3940 series & 3976 series CVR-TRO must be provided with heat activated locking pins as follows: (A) In the lower side of the door at the latch corner for 45 minute rated single and standard & double egress pairs door configurations and (B) In the bottom of the door at the bottom latch corner for 60 & 90 minute rated single and standard & double egress pairs door configurations.  Exception: No pins required in 20 minute with & without hose stream. The 3976 in 45-90 minute applications requires special midrail construction contact Adams Rite for details.
Limitations:
Steel door installed in 16 gauge or heavier steel frames.
 
MAXIMUM SIZES
STANDARD PAIR
8’-0” wide X 10’-0” high
DOUBLE EGRESS PAIR (up to 1-1/2 hr)
8’-0” wide X 10’-0” high
DOUBLE EGRESS PAIR (3 hr)
8’-0” wide x 8’-0” high
Evaluated to the following...
Unless otherwise noted, all assemblies listed in this section have been evaluated for conformance to the following standards:
ASTM-E152, Methods of Fire Tests of Door Assemblies
ASTM-E2074-00
CAN4-S104(ULC-S104), Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods of Fire Tests of Door Assemblies
UBC-7-2-94, Uniform Building Code
UBC-7-2-97, Uniform Building Code
UL-10(b), Fire Tests of Door Assemblies
UL-10(c), Fire Tests of Door Assemblies
and are installed in accordance with the following:
NFPA-80, Fire Windows & Doors 
Manufacturer's Instructions
All assemblies are identified by a label or marking bearing the product's name and the Warnock Hersey Certification Mark.
Listing Report Return to Search
Attributes
CriteriaCAN / ULC S104 (2015) (R2020)
CriteriaUL 10(c) (2016)
CriteriaUL 10(b) (2008) (R2015)
CriteriaNFPA 252 (2017)
CSI Code08 70 00 Hardware
Fire Resistance45 Min Neutral Pressure
Fire Resistance90 Min Neutral Pressure
Fire Resistance3 Hour Neutral Pressure
Fire Resistance60 Min Neutral Pressure
Fire Resistance45 Min Positive Pressure
Fire Resistance90 Min Positive Pressure
Fire Resistance60 Min Positive Pressure
Fire Resistance3 Hour Positive Pressure
Fire Resistance20 Min Neutral Pressure
Fire Resistance20 Min Positive Pressure
Listing SectionDOOR & FRAME HARDWARE
Spec ID26168
SwingSingle Swing
SwingStandard Pairs
SwingDouble Egress
Design Documents
No Results
Public Documents