Steel-Faced (16, 18 gauge) (727) (Mineral Core Type), Swinging Flush Door for installation in 3 hour locations. For use in listed (3-sided) 16 gauge welded or KD steel frames meeting UL-63 or as per frame manufacturer's listing(s).
Limitations*: Mortise or Cylindrical Latches with maximum 5" backset/Surface-Mounted Vertical Rod fire exit devices/Rim-Type fire exit devices/Deadbolts/Surface Bolts/Automatic Flush Bolts (90 minute maximum)/Surface-Mounted Closers/Surface-mounted Protection plates/Surface-Mounted or Mortised Door Bottoms/Astragal Required on Pairs/Temperature Rise - 250°F at 30 minutes/Vision Kit (See table below).
Configuration
|
Maximum Size*
|
Single Swing |
4'0" wide x 8'0" high |
Standard Pairs |
8'0" wide x 8'0" high |
Double Egress Pairs |
8'0" wide x 8'0" high |
*See manufacturer's installation instructions for additional information on Smoke and Draft Control, size restrictions and limitations.
VISION PANELS FOR ALL DOORS
NOTE: In order to preserve temperature rating on doors, clear view cannot exceed 100 sq. in. if listed fire protection rated glazing is used. If clear view exceeds 100 sq. in. and fire protection rated glazing is used temperature rating on door is voided. Listed fire resistance rated glazing (Marked D-H-W) may be used in accordance with the glazing manufacturer's listing and with respect to the size limitations referenced below.
Wired Glass:
Rating |
Max. Visible Area |
Comments |
60/90 minute |
100 sq.in. |
Channel Not required; Pemko FG3000 and Pilkington/Asahi Glass |
60/90 minute |
552 sq.in. Single
1872 sq.in. Multiple |
Channel Required; Pemko FG3000 and Pilkington/Asahi Glass |
20/45 minute |
2856 sq.in. Single/Multiple |
Channel Required; Pemko FG3000 and Pilkington/Asahi Glass |
20/45 minute |
1296 sq.in. |
Channel Not required; Closed Cell Glazing Material and Pilkington/Asahi Glass |
20 minute without hose |
2994 sq.in. |
Channel Required; Closed Cell Glazing Material and Pilkington/Asahi Glass |
FireLite® Glazing:
Rating |
Max. Visible Area |
Comments |
3 hour |
100 sq.in. |
Channel Not Required |
60/90 minute |
1296 sq.in. |
Channel Not Required |
90 minute Temp rise |
100 sq.in. |
Temp Rise Door |
45/60 minute |
1296 sq.in. |
|
20 minute without hose |
2835 sq.in. |
Without Hose |
Evaluated to the following...
This category includes doors evaluated without an edge-sealing system between the door and frame. It also includes doors evaluated with a sealing system incorporated (concealed or visible) into the edge of the door by the licensed manufacturer or machining distributor.
Meeting edges of pairs may require an astragal or an edge-sealing system. Please refer to individual door listings.
These doors are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in the accordance with the frame manufacturer's individual listing.
All doors listed in Category A are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.
All doors in this category are identified by a label or marking bearing the wording, "Listed Fire Door", a time interval, a temperature rise rating, a serial number and the Warnock Hersey Certification Mark and "UL 10C / NFPA 252 / CAN/ULC S104".