Intertek Directory of Building Products

Titan Steel Door, LLC - 45 Minute Metal Detention Fire Doors PP Company: Titan Steel Door, LLC

DOORS

Swing Type Fire Door (12, 14 gauge)(Steel-Faced)(Vertically Steel-Stiffened) for installation in single or pairs in 20 minute and 45 minute, positive pressure, masonry wall locations.

 

Swing Maximum Size of Openings Glass Lights
Single Only 4'0" wide x 8'0" high Max 100 sq.in. for listed wire glass; Max 1302 sq.in. for listed ceramic glass*

 

*NOTE: Maximum 1302 sq.in. applies to Pyran Platinum ceramic glazing and any listed ceramic glazing approved for a maximum area of equal or greater. Maximum area limited by the listed glazing specifications in all other cases.

Limitations: Active Leaf-Single Point Latches (Mortise or Cylindrical) or Fire Exit Hardware/Inactive Leaf-Top and bottom Automatic or Manual Flush Bolt/Astragal/Surface Mounted Vertical Rod fire Exit Device for Active-Active Leaf.

Evaluated to the following:

Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:

CAN/ULC-S104, Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods for Fire Tests of Door Assemblies
UL-10(c), Positive Pressure Fire Tests of Door Assemblies

and are installed in accordance with the following:
NFPA-80, Fire Doors and Windows

Manufacturer's Instructions.
All assemblies are identified by a label or marking bearing the wording, "Listed (Product)", a time interval, temperature rise (if applicable), a serial number and the WHI Certification Mark.

Doors are eligible to bear the “S” (for Smoke & Draft Control assemblies) if a listed “Category H - Smoke & Draft Control Gasket” has been applied to the assembly. Please refer to Category H for individual gasket manufacturer’s listings.

Listing Report Return to Search
Attributes
CriteriaNFPA 252 (2008)
CriteriaUL 10(c) (2009)
CriteriaCAN / ULC S104 (2010)
CriteriaNFPA 252 (2012)
CriteriaCAN / ULC S104 (2015) (R2020)
CriteriaUL 10(c) (2016)
CSI Code08 11 00 Metal Doors and Frames
Fire Resistance20 Min w/Hose Positive Pressure
Fire Resistance45 Min Positive Pressure
Listing SectionCATEGORY A - DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Spec ID26556
SwingSingle Swing
Design Documents
No Results
Public Documents
No Results