ClarkDietrich Steel 'H' Stud and C-Runner Fire-Resistance-rated Area Separation Wall Assemblies Company: ClarkDietrich

PRODUCT DESCRIPTION:

'H' Stud, galvanized steel, roll-formed and punched, minimum 2-1/2" deep by 0.019" thick.
C-Runner, galvanized steel, roll-formed and punched, minimum 2-1/2" deep by 0.019" thick.

SYSTEM DESCRIPTION (unless otherwise noted, fire ratings apply to tests conducted on both sides):
  • Assembly Rating:  2-hours, Non-bearing symmetrical area separation wall, Design weight: 14 psf (refer to Designs CD/WA 120-03).
  • Assembly Rating:  2-hours (with exposure on fire side only).  Restricted load bearing non-symmetrical wall tested with gypsum shaftliner under load simulating a wall height of 50 feet.  Design weight: 11 psf (refer to Designs CD/WA 120-04).
Designs listed are minimum construction requirements to achieve fire rating.

Evaluated to the following (Unless otherwise noted, the assemblies in this section have been evaluated for conformance to the following standards):

ASTM E119, Standard Methods of Fire Tests of Building Construction and Materials
CAN/ULC S101, Standard Method of Fire Endurance Tests of Building Construction and Materials
UL 263, Fire Tests of Building Construction and Materials
 
CERTIFIED FOR USE IN THE FOLLOWING ASSEMBLIES
Wall Assembly Design Number‡
Corresponding Assembly Listee
CD/WA 120-03 ClarkDietrich 
CD/WA 120-04 ClarkDietrich 
CB/WA 120-03† Continental Building Products
CB/WA 120-04† Continental Building Products
GP/WA 120-03† Georgia-Pacific Gyspum
GP/WA 120-04† Georgia-Pacific Gyspum
‡Designs are based on, and supported by, proprietary test reports.  The test reports further define proprietary design details which make these listings applicable only to the specified products manufactured by the listed manufacturer.

†Designs are located in the respective Continental Building Products or Georgia-Pacific-Gypsum Listing Reports
Listing Report Return to Search
Attributes
AssembliesFire Rated Wall Assembly Un-Loaded
AssembliesFire Rated Wall Assembly Loaded
CriteriaUL 263 (2011)
CriteriaCAN / ULC S101 (2014)
CriteriaASTM E119 (2016)
CSI Code09 22 16.13 Non-Structural Metal Stud Framing
CSI Code09 21 16.33 Gypsum Board Area Separation Wall Assemblies
Fire Resistance2 Hour Wall Assembly
Listing SectionADDITIONAL COMPONENTS FOR WALL ASSEMBLIES
Listing SectionWALL ASSEMBLIES
Spec ID26662