CATEGORY A - DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Wood Core Type (Particle Board or Wood Block), Swinging Flush Design Fire Door (with hose stream), including double egress, for installation in 20 minute locations . For use in any "Category C - Standard" frame. The doors may also be installed in frames listed in "Category C - Proprietary" in accordance with the door manufacturer's installation instructions.
Limitations
Mortise or Cylindrical Latches with up to a 2-3/4" backset/Deadbolts/Surface Mounted or Mortise, Rim Type Fire Exit Device/ Surface Mounted Vertical Rod or Concealed Vertical Rod Fire Exit Hardware/Surface Mounted Vertical Rod Fire Exit Device Less Bottom Rod (LBR)/Automatic or Manual, Mortised or Surface Mounted Flush Bolts/Door Closer/Concealed Closer Arm/Surface-Mounted or Mortised Door Bottoms/Viewers/Electric Race Way installed below the positive pressure line (40" from bottom of door)/ Edge Guards/ Protection Plates up to 16"/Plant-Ons/Vision Panels - 1296 sq.in.
Evaluated to the following...
This category includes doors evaluated with a sealing system incorporated (concealed or visible) into the edge of the door by the licensed manufacturer or machining distributor. It also includes doors evaluated without an edge-sealing system between the door and frame.
Meeting edges of pairs may require an astragal or an edge-sealing system. Please refer to individual door listings.
These doors are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in the accordance with the frame manufacturer's individual listing.
All doors listed in Category A are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.
All doors in this category are identified by a label or marking bearing the wording, "Listed Fire Door", a time interval, a temperature rise rating, a serial number and the Warnock Hersey Certification Mark and "UBC-7-2-97/UL-10C".
CATEGORY B - DOORS - ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Wood Core Type (Particle Board, Wood Block or LDF), Swinging Flush Design Fire Door (with hose stream), including double egress, for installation in 20 minute locations. For use in any "Category C - Standard" frame. The doors may also be installed in frames listed in "Category C - Proprietary" in accordance with the door manufacturer's installation instructions.
Limitations
Mortise or Cylindrical Latches with up to a 2-3/4" Backset/Deadbolts/Surface Mounted or Mortise, Rim Type Fire Exit Hardware/Surface Mounted or concealed Vertical Rod Fire Exit Hardware/Surface Mounted Vertical Rod Fire Exit Device Less Bottom Rod (LBR)/Automatic or Manual Mortised or Surface Mounted Flush Bolts/Door Closer/Concealed Closer Arms/Surface-Mounted or Mortised Door Bottoms/Viewers/Electric Race Way when installed below the positive pressure plane (40" from bottom of door)/Edge Guards/ Protection Plates up to 16"/Plant-Ons/Vision Panels - 1296 sq.in.
Evaluated to the following...
This category includes doors evaluated with an edge-sealing system (Category G) field-applied to the labeled frame or door. The application of the edge-sealing system does not require any machining of the frame or door. Please refer to "Category G - Edge-Sealing System" for individual manufacturer's listings.
These assemblies are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in the accordance with the frame manufacturer's individual listing.
All doors listed in Category B are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.
All doors in this category are identified by a label or marking bearing the wording, "Listed Fire Door", a time interval, a temperature rise rating, a serial number and the Warnock Hersey Certification Mark and "UBC-7-2-97/UL-10C".
SIZE LIMITATIONS
Standard pairs require at least 3-point latching
POSITIVE PRESSURE DOORS (1-3/4" +/- 1/16" thick)
|
Single Swing |
Standard Pair |
Double Egress |
Category G Edge Seal with Particleboard, Agristrand or Agri-Fiber Core |
4'0" wide x 9'0" high |
8'0" wide x 9'0" high |
Not allowed |
22 pcf LDF Core* |
3'0" wide x 8'0" high |
Not allowed |
Not allowed |
*NOTE: Category B doors only. Must be installed in masonry wall assemblies.
NEUTRAL PRESSURE DOORS (1-3/4" +/- 1/16" thick)
|
Single Swing |
Standard Pair |
Double Egress |
Particle Board, Agristrand, or Agrifiber Core |
4'0" wide x 10'0" high |
8'0" wide x 10'0" high |
8'0" wide x 9'0" high |
22 pcf LDF Core |
3'0" wide x 8'0" high |
Not allowed |
Not allowed |
NOTES:
-
Door and transom not allowed.
-
Doors (with Category G BASF) installed in non JELD-WEN frame is without hose stream rating.
-
Dutch door not allowed.
-
Minimum 5" wide G-P Firestop I stiles are required for standard pair or double egress pair doors with concealed vertical rod fire exit device.
-
3" G-P Firestop or Tectonite required for bottom rail when mortised door bottoms are to be installed.
-
Use of MDF top rails to a maximum door size:
-
Single Swing (maximum): 4'0" wide x 9'0" high x 1-3/4" thick
-
Standard Pairs (maximum): 8'0" wide x 9'0" high by 1-3/4" thick
-
Double Egress: Not Allowed