JELD-WEN 20 Min Flush Fire Door (without hose stream) Company: JELD-WEN, Inc.

CATEGORY A - DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED

Wood Core Type (Particle Board or Wood Block), Swinging Flush Design Fire Door (without hose stream),  including double egress, for installation in 20 minute locations . For use in any "Category C - Standard" frame. The doors may also be installed in frames listed in "Category C - Proprietary" in accordance with the door manufacturer's installation instructions.

 

Limitations

Mortise or Cylindrical Latches with up to a 2-3/4" backset/Deadbolts/Surface Mounted or Mortise, Rim Type Fire Exit Device/ Surface Mounted or Concealed Vertical Rod Fire Exit Hardware/Surface Mounted  Vertical Rod Fire Exit Device Less Bottom Rod (LBR)/Automatic or Manual, Mortised or Surface Mounted Flush Bolts/Door Closer/Concealed Closer Arm/Surface-Mounted or Mortised Door Bottoms/Viewers/Electric Race Way installed below the positive pressure line (40" from bottom of door)/ Edge Guards/ Protection Plates up to 16"/Plant-Ons/Vision Panels - 1296 sq.in.

Evaluated to the following...

This category includes doors evaluated with a sealing system incorporated (concealed or visible) into the edge of the door by the licensed manufacturer or machining distributor. It also includes doors evaluated without an edge-sealing system between the door and frame.


Meeting edges of pairs may require an astragal or an edge-sealing system. Please refer to individual door listings.


These doors are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in the accordance with the frame manufacturer's individual listing.


All doors listed in Category A are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.


All doors in this category are identified by a label or marking bearing the wording, "Listed Fire Door", a time interval, a temperature rise rating, a serial number and the Warnock Hersey Certification Mark and "UBC-7-2-97/UL-10C".

CATEGORY B - DOORS - ADDITIONAL EDGE-SEALING SYSTEM REQUIRED

 
 

Wood Core Type (Particle Board or Wood Block), Swinging Flush Design Fire Door (without hose stream), including double egress, for installation in 20 minute locations. For use in any "Category C - Standard" frame. The doors may also be installed in frames listed in "Category C - Proprietary" in accordance with the door manufacturer's installation instructions.

 

Limitations

Mortise or Cylindrical Latches with up to a 2-3/4" Backset/Deadbolts/Surface Mounted or Mortise, Rim Type Fire Exit Hardware/Surface Mounted or concealed Vertical Rod Fire Exit Hardware/Surface Mounted Vertical Rod Fire Exit Device Less Bottom Rod (LBR)/Automatic or Manual Mortised or Surface Mounted Flush Bolts/Door Closer/Concealed Closer Arms/Surface-Mounted or Mortised Door Bottoms/Viewers/Electric Race Way installed below the positive pressure line (40" from bottom of door)/Edge Guards/ Protection Plates up to 16"/Plant-Ons/Vision Panels - 1296 sq.in.

Evaluated to the following...

This category includes doors evaluated with an edge-sealing system (Category G) field-applied to the labeled frame or door. The application of the edge-sealing system does not require any machining of the frame or door. Please refer to "Category G - Edge-Sealing System" for individual manufacturer's listings.

 

These assemblies are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in the accordance with the frame manufacturer's individual listing.

 

All doors listed in Category B are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.

 

All doors in this category are identified by a label or marking bearing the wording, "Listed Fire Door", a time interval, a temperature rise rating, a serial number and the Warnock Hersey Certification Mark and "UBC-7-2-97/UL-10C".

SIZE LIMITATIONS

Standard pairs require at least 3-point latching

POSITIVE PRESSURE DOORS (1-3/4" +/- 1/16" thick)

 

  Single Swing Standard Pair Double Egress
Category G Edge Seal

4'0" wide x 9'0" high

8'0" wide x 9'0" high

Not Allowed

BASF Encapsulated Palusol

4'0" wide x 8'0" high

8'0" wide x 8'0" high

8'0" wide x 8'0" high

BASF Palusol Under Lipping

4'0" wide x 10'0" high

8'0" wide x 10'0" high

8'0" wide x 9'0" high

Category G Edge Seal with LDF Core

3'0" wide x 8'0" high

6'0" wide x 8'0" high

6'0" wide x 8'0" high

 

NEUTRAL PRESSURE DOORS (1-3/4" +/- 1/16" thick)

 

  Single Swing Standard Pair Double Egress
All Core Types 4'0" wide x 10'0" high 8'0" wide x 10'0" high 8'0" wide x 9'0" high

 

NOTES:

  1. Door and transom not allowed.
  2. All doors installed in JELD-WEN wood frames are with Hose Stream.
  3. Dutch door not allowed.
  4. Minimum 5" wide G-P Firestop I stiles are required for standarad pair or double egress pair doors with concealed vertical rod fire exit device.
  5. 3" G-P Firestop or Tectonite  required for bottom rail when mortised door bottoms are to be installed. 
  6. Use of MDF top rails to a maximum door size:
    • Single Swing (maximum): 4'0" wide x 9'0" high x 1-3/4" thick
    • Standard Pairs (maximum): 8'0" wide x 9'0" high by 1-3/4" thick
    • Double Egress: Not Allowed
Listing Report Return to Search
Attributes
CriteriaUL 10(c) (1998)
CriteriaNFPA 252 (1999)
CriteriaNFPA 252 (2008)
CriteriaUL 10(b) 2008 (R2009)
CriteriaUL 10(c) (2009)
CriteriaNFPA 252 (2012)
CSI Code08 10 00 Doors and Frames
Fire Resistance20 Min w/out Hose Stream PP Cat A Door
Fire Resistance20 Min w/out Hose Stream NP
Fire Resistance20 Min w/out Hose Stream PP Cat B Door
Listing SectionCATEGORY B - DOORS - ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Listing SectionCATEGORY A - DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Spec ID26818
SwingSingle Swing
SwingStandard Pairs
SwingDouble Egress
Design Documents
No Results
Public Documents
No Results