Mineral Core Type (16, 18, 20 gauge) (Steel-Faced), Swinging Flush Design Fire Door for installation singly or in pairs in 1-1/2 hour locations.
Limitations: Mortise or Cylindrical Latches/Mortised or Rim Type Fire Exit Hardware/Concealed & Surface Mounted Vertical Rod Type Fire Exit Hardware/Mortised and/or Concealed & Surface Mounted Top & Bottom Bolts/Temperature Rise - 250°F @ 30 minutes, 450°F (250°C) @ 60 minutes.
Maximum Size of Openings: |
Singles - 4'0" wide x 8'0" high Pairs - 8'0" wide x 8'0" high, astragal required Double Egress - 8'0" wide x 8'0" high, astragal required |
Maximum Lite: |
100 sq.in. per door leaf |
Mineral Core Type (16, 18, 20 gauge) (Steel-Faced), Swinging Flush Design Fire Door for installation singly or in pairs in 3 hour locations.
Limitations: Mortise or Cylindrical Latches/Mortised or Rim Type Fire Exit Hardware/Concealed & Surface Mounted Vertical Rod Type Fire Exit Hardware/Mortised and/or Concealed & Surface Mounted Top & Bottom Bolts/Temperature Rise - 250°F @ 30 minutes, 450°F (250°C) @ 60 minutes.
Maximum Size of Openings: |
Singles - 4'0" wide x 8'0" high Pairs - 8'0" wide x 8'0" high, astragal required |