Intertek Directory of Building Products

Fire Lock Data: Firelock Modular Panel Company: Firelock Data Protection Systems

 
Firelock Insulated Modular Panels are used to construct fire resistive and high temperature insulative vaults for the purpose of protecting documents, electronic media, or other items of value. They consist of an expanded metal interior surface. The panels measure 6 in. in thickness. The UNVENTILATED vault system incorporates a Listed internal fire door and a Listed external fire door, and a through-penetration firestop system for cable transit. The interior surface and exterior surface are clad with 1 layer of 5/8-in. Type X gypsum wallboard.
Tests
ASTM E 119
Reference Listed Design Section
UL 72 Reference Listed Design Section
Minimum Unventilated Vault Size Rating
9 ft. x 9 ft. Class 125 - 2 hour
9 ft. x 9 ft. Class 350 - 4 hour
12 ft. x 12 ft. Class 150 - 3 hour
18 ft. x 18 ft. Class 125 - 3 hour
20 ft. x 20 ft. Class 150 - 4 hour
28 ft. x 28 ft. Class 125 -4 hour
 
ASTM E 814 Cable Penetration Assembly
Design No. T-Rating F-Rating
NBW 706 3-1/2 hour 5 hour
Listing Report Return to Search
Attributes
CriteriaASTM E119 (Engulfment)
CriteriaASTM E814
CriteriaUL 72 (2001)
CSI Code13 00 00 Special Construction
CSI Code13 20 00 Special Purpose Rooms
Fire Resistance2 Hour Fire Rated
Fire Resistance3 Hour Fire Rated
Fire Resistance4 Hour Fire Rated
Listing SectionADDITIONAL COMPONENTS FOR WALL ASSEMBLIES