Intertek Directory of Building Products

Ceco Volume IV - Fire Door Frame Specs Company: Ceco Door Products

DOOR FRAMES
Pressed Steel Door Frame (14, 16 or 18 gauge) (DS/S Series*) (Knock-Down) for installation in 1-1/2 hour steel/wood stud drywall openings
Maximum Size of Openings: Singles - 4'0" wide x 9'0" high
Pairs - 8'0" wide x 9'0" high
Minimum Throat Opening: 3-1/2"
Pressed Steel Door Frame (12, 14, 16 or 18 gauge) (S/C Series*) (Knock-Down or Welded Up) for installation in 3 hour steel/wood stud drywall or masonry openings.
Maximum Size of Openings: Singles - 4'0" wide x 10'0" high
Pairs - 8'0" wide x 10'0" high
Minimum Throat Opening: 3"
Fabrication Standard: 3821
Pressed Steel Door Frame (18 gauge Base Frame & 22 gauge Trim) (SR Series*) (Knock-Down) for installation in 1-1/2 hour steel/wood stud drywall openings.
Maximum Size of Openings: 3'6" wide x 7'0" high
Minimum Wall Thickness: 3-3/8"
Pressed Steel Side Light Door Frame (14 or 16 gauge) (Welded Up) for installation in 20 minute locations (tested without hose stream) in steel/wood stud drywall or masonry openings.
Maximum Overall Dimensions: 1) Drywall - 13'2" wide x 11'7" high
2) Masonry- 13'6" wide x 12'0" high
Maximum Door Opening: 8'0" wide x 9'0" high
Maximum Side Light Opening: 109-3/4" wide x 109-3/4" high clear view
Minimum Throat Dimensions: 3-1/2"
Maximum Exposed Glass Area: 5268 sq.in
Pressed Steel Side Light Door Frame (14 or 16 gauge) (Welded Up) for installation in 1 hour locations in steel/wood stud drywall or masonry openings.
Limitations: "Firelight" listed glazing (or equivalent) must be used, and prior approval must be obtained from the authority having jurisdiction, as applicable code requirements may vary. All the listing conditions for the glazing must be satisfied.
 
Maximum Overall Dimensions: 10'2" wide x 10'1" high
Minimum Wall Thickness: 4-7/8"
Maximum Clear View Glazing Area: 2721 sq.in. (Note: Refer to limitations of the listed glazing). Stop Height: 5/8"
Pressed Steel Side Light Door Frame (14 or 12 gauge) (Welded Sections or Fully Welded) for installation in 45 minute locations in steel/wood stud drywall or masonry openings.
Limitations: Side Lights require Velga Contraflam CF-45* Intertek labeled glazing per O'Keeffe's, Inc. glazing installation instructions.
 
Maximum Overall Dimensions: 120" wide x 109-3/8" high
Maximum Door Opening: 4'0" wide x 9'0" high
Maximum Individual Side Light Opening: 42-3/4" wide x 93-1/2" high Clear View and 3997 square inches Clear View Area.
Minimum Side Light Stop Height: 1-1/4"
Minimum Throat Opening: 3-3/4"
Pressed Steel Door Frame (14 gauge base frame & 16 gauge trim) (Retro-Tech AF Series*) (Knock-Down or Welded Up) for installation in 1-1/2 hour steel/wood stud drywall or masonry openings.
Limitations: Some designs are not approved for 1-1/2 hour rating or maximum sizes shown 
Maximum Size of Openings: Singles - 4'0" wide x 7'2" high
Pairs - 6'0" wide x 7'2" high
Pressed Steel Side Light Door Frame (14 or 16 gauge) (Welded Up) for installation in 45 minute locations in steel/wood stud drywall or masonry openings.
 
Maximum Door Opening: 8'0" wide x 9'0" high
Maximum Overall Dimensions: Masonry - 13'6" wide x 12'0" high with 30" wide x 54" high maximum side light clear view
Drywall - 11'4" wide x 10'0" high with 30" wide x 54" high maximum side light clear view
Masonry or Drywall - 9'2-1/2" wide x 10'0" high with 51-1/2" wide x 54" high maximum side light clear view
Minimum Throat Dimension: 3-1/2"
Maximum Exposed Glass Area: 1296 sq.in.
Pressed Steel Door Frame with Transom and/or Side Light (14, 16 gauge) (Welded Up) for installation in up to 1-1/2 hour locations in steel/wood stud drywall or masonry openings.
Limitations: "PyroStop" listed glazing must be used. Prior approval must be obtained from the Authority Having Jurisdiction as applicable code requirements may vary. All listings conditions for the glazing must be satisfied.
 
Rating Maximum Size Masonry Maximum Size Masonry Maximum Visible Glazing Panel Area
20 Minute 13'6" x 12'0" 13'2" x 11'7" 1860.5*
45 Minute 13'6" x 12'0" 12'10" x 11'4" 4290*
60 Minute 10'2" x 10'1" 10'2" x 10'1" 4290*
90 Minutes 13'6" x 12'0" 11'4" x 10'0" 1860.5*
*Note: Refer to limitations of the listed glazing
Stop Height: 5/8"
*Manufacturer's Designation
 
Note: For additional information please refer to Openings listings.

 
Maximum throat size for all frames is 18 inches.  For throats over 13 inches thick, two anchors are required at each anchoring location as specified in the manufacturing section of this Listing.  Frames with a throat over 13 inches must be fully grouted for 3 hour fire resistance applications.  Grouting is optional for 90 minutes or less fire resistance applications (masonry or drywall walls) for frames with a throat over 13 inches. 
 
Evaluated to the following...
Unless otherwise noted, assemblies in this section have been tested to the following standards:
NFPA-252, Standard Methods of Fire Tests of Door Assemblies; UL-10(b), Fire Tests of Door Assemblies;
and are installed, unless otherwise noted, in accordance with the following:
NFPA-80, Fire Doors & Windows.
Manufacturer's Instructions.
Listed maximum sizes of lights are based on sizes tested and may exceed local code requirements.
 
All frames are identified by either a label or embossed marking bearing the wording "Listed (Product)" and the WHI Certification Mark. Frames rated for less than 3 hours also bear the time interval. Frame labels that do not include a time interval are rated for 3 hours.
 
FIRE WINDOW FRAMES
Pressed Steel Fire Window Frame (14, 16 gauge) (Knock-Down or Welded Up) for installation in 3/4 hour locations in steel/wood stud drywall or masonry openings. 
Maximum Overall Dimensions: Drywall: 11'4" wide x 10'0" x 12'0" high when resting on floor or concrete.
Masonry: 13'6" wide x 12'0" x 12'0" high when resting on floor or concrete.
Drywall: 9'2-1/2" wide x 4'11-1/2" high when installed above floor.
Maximum Throat Opening: 3-1/2"
Maximum Exposed Glass Area: 1,296 sq.in.
 
Pressed Steel Fire Window Frame (14, 16 gauge) (Knock-Down or Welded Up) for installation in 20 minute locations (tested without hose stream) in steel/wood stud drywall or masonry openings.
 
Maximum Overall Dimensions: Drywall: 13'2" wide x 10'0" high when resting on floor.
Drywall: 13'2" wide x 9'7" high when installed above floor.
Masonry: 13'6" wide x 12'0" high when resting on floor or concrete.
Maximum Throat Opening: 3-1/2"
Maximum Exposed Glass Area: 5,268 sq.in. - Not for use in Canada.
Pressed Steel Fire Window Frame (14, 16 gauge) (Welded Up) for installation in 1 hour locations in steel/wood stud drywall or masonry openings.
Limitations: "Firelite" listed glazing or equivalent must be used. Prior approval must be obtained from the Authority Having Jurisdiction as applicable code requirements may vary. All the listing conditions for the glazing must be satisfied.
 
Maximum Overall Dimensions: Drywall or Masonry: 10'2" wide x 10'1" high when resting on floor.
Drywall or Masonry: 9'2-1/2" wide x 4'11-1/2" high when installed above floor.
Minimum Wall thickness: 4"
Maximum Clear View Area of Glazing: 2,721 sq.in.
Note: Refer to 'Limitations' of the listed glazing. Stop Height: 5/8"
Pressed Steel Fire Window Frame (14, 12 gauge) (Fully Welded) for installation in 3/4 hour locations in steel/wood stud drywall or masonry openings.
Limitations: Lights require Vegla Contraflam CF-45* ITS labeled glazing per O'Keeffe's, Inc. glazing installation instructions.
 
Maximum Overall Dimensions: 120" wide x 109" high when resting on floor.
108" wide x 51-1/2" high when installed above floor.
110-1/2" wide x 59-1/2" high when installed above floor.
Maximum Individual Light Openings: 42-3/4" wide x 93-1/2" high Clear View and 3,997 sq.in. Clear View Area.
100" wide x 46" Clear View and 4,600 sq.in. Clear View Area.
42-3/4" side x 56-3/4" Clear View and 2,426 Clear View Area.
Minimum Stop Height: 1-1/4"
Minimum Throat Opening: 3-3/4"
*Manufacturer's Designation

Evaluated to the following...
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
UL-9, Fire Tests of Window Assemblies.
and are installed, unless otherwise noted, in accordance with the following:
NFPA-80, Fire Doors & Windows.
Manufacturer's Instructions.
Listed maximum sizes of lights are based on sizes tested and may exceed local code requirements.
 
All assemblies are identified by a label or marking bearing the wording "Listed Fire Window Frame", a time interval, a serial number and the WHI Certification Mark.
 
CATEGORY C - STANDARD FRAMES
Pressed Steel Transom and/or Side Light Door Frame Assembly (14, 16 gauge) for installation in up to 45 minute locations in steel/wood stud drywall or masonry openings. Glazing Types: Listed 1/4" wired glass or FireLite®.
 
Maximum Size of Openings: Masonry: 13'6" wide x 12'0" high
Drywall: 11'4" wide x 10'0" high
Maximum Visible Area per Light 1296 sq.in.
Maximum Visible Width per Light 54"
Maximum visible Height per Light 54"
Pressed Steel Fire Window Frame (14, 16 gauge) for installation in up to 45 minute locations in steel/wood stud drywall or masonry openings. Glazing Types: Listed 1/4" wired glass or FireLite®.
 
Maximum Size of Openings: Masonry: 13'6" wide x 12'0" high
Drywall w/Masonry Sill: 11'4" wide x 10'0" high
Drywall: 9'2-1/2" wide x 10'0" high
Maximum Visible Area per Light 1296 sq.in.
Maximum Visible Width per Light 54"
Maximum visible Height per Light 54"

Pressed Steel Frame (14, 16 gauge) for installation in up to 90 minute locations in steel/wood stud drywall or masonry opening.
Maximum Size of Openings: Single: 4'0" wide x 10'0" high
Pairs: 9'0" wide x 10'0" high
Double Egress: 9'0" wide x 10'0" high
Minimum Throat Openings: 5"

Pressed Steel Frame (14, 16 gauge) (Adjustable) for installation in up to 90 minute locations in steel/wood stud drywall or masonry opening.
Maximum Size of Openings: Single: 4'0" wide x 8'0" high
Minimum Throat Opening: 3-3/4"

Evaluated to the following...

This category includes frames based on UL-63 and includes sidelight/transom assemblies. These frames are qualified for use in positive pressure assemblies, with Category A doors, or with Category B doors utilizing Category G edge-sealing systems. These frames, when installed in pairs in drywall construction, shall have anchors installed in the head section, minimum 24" on center. These listings will not reference specific door types, as all door types are eligible.

All frames in this category are identified by a label or marking bearing the wording, "Listed Fire Door Frame", and the Warnock Hersey Certification Mark. Frames rated at less than 3 hours will have a time interval noted on the label/marking.
Listing Report Return to Search
Attributes
CriteriaUL 9 (2009)
CriteriaUL 263 (2011)
CriteriaCAN / ULC S104 (2015) (R2020)
CriteriaUL 10(b) (2008) (R2015)
CriteriaUL 10(c) (2016) Ed. 3 (R:27 May 2021)
CriteriaNFPA 252 (2022)
CSI Code08 11 00 Metal Doors and Frames
CSI Code08 50 00 Windows
Fire Resistance20 Min NP Fire Doorframe with Transom and/or Sidelite
Fire Resistance20 Min w/out Hose Stream NP
Fire Resistance20 Min PP Category C Proprietary Frame
Fire Resistance45 Min PP Category C Proprietary Frame
Fire Resistance45 Min NP Fire Doorframe
Fire Resistance45 Min NP Fire Doorframe with Transom and/or Sidelite
Fire Resistance90 Min Positive Pressure
Fire Resistance3 Hour Positive Pressure
Fire Resistance60 Min NP Fire Doorframe
Fire Resistance60 Min NP Fire Doorframe with Transom and/or Sidelite
Fire Resistance3 Hour NP Fire Doorframe
Fire Resistance90 Min NP Fire Doorframe
Fire Resistance90 Min NP Fire Doorframe with Transom and/or Sidelite
Fire Resistance60 Min PP Category C Proprietary Frame
Listing SectionCATEGORY C - PROPRIETARY FRAMES
Listing SectionFIRE WINDOW FRAMES
Spec ID27124
Design Documents
No Results
Public Documents