Pressed Steel Fire Window Frame (16, 14, 12 gauge) (Knock-Down or Welded Up) for installation singly or pairs (including Double Egress) in 20 or 45 minute locations in steel/wood stud drywall or masonry openings.
Limitations
Visible Area
|
Groove Depth
|
300 sq.in. |
1/2" |
400 sq.in. |
9/16" |
500 sq.in. |
5/8" |
600 sq.in. |
11/16" |
1296 sq.in. |
3/4" |
Maximum Overall Dimensions: |
7'0" wide x 10'0" high |
Visible Glazing (each light) |
1296 sq.in. |
Maximum Width or Height (each light) |
54" |
Maximum Throat Opening: |
4" Min. and 12-3/4" Max. |
Evaluated to the following...
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
ASTM-E163, Methods of Fire Tests of Fire Window Assemblies.
CAN4-S106, Standard Method for Fire Tests of Window & Glass Block Assemblies.
NFPA-257, Standard Method for Fire Tests of Fire Window Assemblies.
UBC-7-4-94, Uniform Building Code.
UL-9, Fire Tests of Window Assemblies.
and are installed, unless otherwise noted, in accordance with the following:
NFPA-80, Fire Doors & Windows.
Manufacturer's Instructions.
Listed maximum sizes of lights are based on sizes tested and may exceed local code requirements.