Section 10: Steelcraft 20-90 Min Fire Window Frame Company: Steelcraft Manufacturing / Schlage Lock Company LLC

PRODUCT COVERED
F, FN, FC, MU, & MC Series fire window frames of the hollow-metal fixed type. The depth of frame jambs shall be for a minimum wall thickness of 2 in. Frames glazed with listed 1/4" wire glass shall be rated for maximum 3/4 hour fire protection unless otherwise indicated in Section General. These window frames are intended to be glazed with 1/4 inch thick Listed wire glass or other Listed glazing material shown in Section General. The glass may be installed at the jobsite or manufacturer’s location in accordance with the glass manufacturer’s requirements.
Listed glazing materials may not exceed the limitations shown in Section General or the limitations of the published listings of the individual glazing material manufacturer. Glass and glazing shall be installed in accordance with the installation instructions of the individual glazing material manufacturer.
Fire window frames may also incorporate panels as specified in Section 7. Panels may be used in conjunction with glass. The frame shall bear the rating of the least rated component.
Frames glazed with 3/16" thick, 5/16” thick or 1” thick (insulated) non-wire Firelite glass by Technical Glass Products, Superlite, Pyrostop, or other approved glass not specifically listed may be rated for 1 hour fire protection. Frames may be rated 1-1/2 hours when using the appropriate Firelite®, Superlite, Pyrostop,
Pyrobel or Verotech Saint-Gobain (Keralite & Swissflam) or other approved glass not specifically listed.
Glass may be installed at the jobsite or manufacturer’s location in in accordance with the glass manufacturer’s requirements.
Evaluated to the following...
Unless otherwise noted, assemblies in this section have been tested to the following standards:
CAN/ULC S104
NFPA 252
UL-10C

Note: Canadian test standards that are referenced in this listing are applicable only to assemblies that have successfully met the requirements of the hose stream portion of the test.
and are installed, unless otherwise noted, in accordance with the following:
NFPA-80, Fire Doors & Windows.
 
Listing Report Certificate of Compliance Return to Search
Attributes
Certificate Date of ExpiryDecember 31, 2026
Certificate Date of Initial RegistrationOctober 23, 2019
Certificate NumberWHI19-20392305
CriteriaUL 9 (2009)
CriteriaNFPA 252 (2012)
CriteriaCAN / ULC S104 (2015) (R2020)
CriteriaUL 10(c) (2016)
CriteriaNFPA 257 (2012)
CriteriaCAN / ULC S106 (2015) Ed.3
CSI Code08 11 00 Metal Doors and Frames
Fire Resistance45 Min Positive Pressure
Fire Resistance90 Min Positive Pressure
Fire Resistance20 Min w/out Hose Positive Pressure
Fire Resistance60 Min Positive Pressure
Listing SectionFIRE WINDOW FRAMES