Intertek Directory of Building Products

Al Kuhaimi Category A Fire Doors Company: Al Kuhaimi Metal Industries, Ltd.

Product Covered:
Al Kuhaimi 45, 60, 90,120 and 180 minutes vertically steel stiffened fire doors (skin thickness 1.2mm, 1.5mm and 2.0mm)
           
Al Kuhaimi 45, 60, 90,120 and 180 minutes Polyurethane and Polystyrene core fire doors (skin thickness 24 gauge, 0.6mm)
 
PRODUCT DESCRIPTION
 
Limitations:

- Door with skin thickness 2.0mm limited to 90 minutes with a maximum height of 2927mm.

- Door with Rock wool density of 50-96 kg/m3 is limited to 90 minutes with additional C channel at the meeting edge. Door with Rock wool density of up to 50 kg/m3 are allowed for up to 180 minutes rating (see sizes below). 

- 1.5mm to 3mm lead lining is allowed for steel stiffened Rockwool infilled door.

- Door skin with Fiber glass insulation of density 18-48 kg/m3 are allowed for up to 180 minutes rating (see sizes below).

- Stiffeners and reinforcement channels can be adhered with the leaf skin using 3M double-sided adhesive tape.

- Concealed/ invisible hinges (ref: 418SSU32), concealed power transfer (ref: CRPT-10 AL) and cable race way (electric conduit) are allowed in steel-stiffened doors with mineral wool or fiber glass infill doors.

- 12 Inch diameter circular vision is limited to maximum 90 minutes.

- 24 inch diameter circular vision is limited to 45minutes

- Pair doors to have astragal unless equipped with two vertical rod exit device. Astragal can be welded or screw fixed to the door leaf.

- Communicating door designs (two door panels in one frame) for the currently listed steel stiffened and PU/honeycomb infill doors are allowed for the same fire rating as of original listed doorset.

- PU/EPS/honeycomb infill doors can use embossed faces. In order to keep the door balanced both the door faces must be same.
 
Configuration Size (Max)
 
A.     Vertically stiffened Hollow metal door (Skin thickness 1.2, 1.5, 2.0mm) for 90 Minutes
 
Details Leaf thickness Maximum Size
Single leaf door 45mm to 56mm 1220 x 3048mm (w x h)
Double leaf door (each) 45mm to 56mm 1220 x 3048mm (w x h)
Double egress door (each) 45mm to 56mm 1220 x 3048mm (w x h)

Limitations: Cylindrical or Mortise Latches with minimum 3/4" Bolt Throw and up to 2-3/4" Backset/Surface Mounted Vertical Rod Mortise Type or Rim Type Fire Exit Hardware/Mortise or Surface Mounted Automatic or Manual Top and Bottom Flush Bolts/Lights - Flat Steel Bar Astragal required on pairs and double egress pairs. Must be installed in 16 gauge or heavier steel frame.
 
B.     Vertically stiffened  Hollow metal door (Skin thickness 1.2, 1.5, 2.0mm) for 3 hours
 
Details Leaf thickness Maximum Size
Single leaf door 45mm to 56mm 1215 x 2995mm (w x h) *
Double leaf door (each) 45mm to 56mm 1215 x 2995mm (w x h) *
Transom panel 45mm to 56mm 2440 x 915mm (w x h)

Limitations: Cylindrical or Mortise Latches with minimum 1/2" latch throw for single and 3/4" latch throw for pairs and up to 2-3/4" Backset/Surface Mounted Vertical Rod Mortise Type or Rim Type Fire Exit Hardware/Mortise or Surface Mounted Automatic or Manual Top and Bottom Flush Bolts/Lights - Flat Steel Bar Astragal required on pairs and double egress pairs. Must be installed in 16 gauge or heavier steel frame.

* For the door height over 2425mm, the following conditions are to be followed:
  1. The assembly shall be locked with a deadlock positioned 500 mm above the door handle – Not applicable for egress application.
  2. For single-leaf doors, fire latch bolts shall be installed with one located 500 mm below the door handle and one at the top horizontal edge.
  3. For double-leaf doors, fire latch bolts shall be installed with one located 500 mm below the door handle, one at mid-height between the handle and the top edge, and one at the top horizontal edge.
 C.     Polyurethane and polystyrene Hollow metal door (Skin thickness 24 gauge , 0.6mm) for 3 hours
 
Single leaf:                              915mm wide x 2135mm high
 
Pair:                                          1828mm wide x 2135mm high

Thickness:                                45mm

Note: Thickness increase to 50mm is allowed for negative pressure (UL 10B) case. 
 
Limitations*: Mortise or Cylindrical Latches with maximum 5” backset/Mortised Exit devices/Surface Mounted Vertical Rod fire exit devices/Rim Type fire exit devices/Deadbolts/Surface Bolts/Automatic Flush Bolts/Surface Mounted Closers/Edge Guards/Surface Mounted Protection Plates/Viewer/Louver (Maximum 24” x 24”)/Vision Light Kit – Maximum 1296 sq.in. using fire-rated glazing/Surface Mounted Door Bottoms/Astragal

Door edge constructions: - Interlock seam joint with welding, seamless full welding edge and seamless with metal putty on the edges. Interlock seam joint with tabs is allowed for maximum 120 minutes fire rating.
 
Glazing:
 
 
Fire Door Rating:
Maximum Area of Glazing (per leaf)  
Maximum* width
 
Maximum height:
Circular Glazing
Maximum diameter/leaf
Multiple Glazing
Maximum area/leaf
45 minutes and below 1296 sq in (0.84 sq m) 36 inch** (915mm) 54 inch ** 1372mm 24 sq inch 1296 sq inch
60 & 90 minutes 1296 sq in (0.84 sq m) 36 inch** (915mm) 54 inch ** 1372mm 12 sq inch 1296 sq inch
120 & 180 minutes                                 100 sq in (0.065 sq m) 12 inch** (304.8mm) 33 inch **(838.2mm) N/A N/A
  
 *Maximum width of glazing further limited by what is allowed based on door width while maintaining minimum edge of door to glazing distance of 150 mm, (150 mm minimum distance also applies to top of door)
  
** 5.5 inches (139.7mm) from door edge to glazing cut out must be maintained (minimum). 1.5mm steel C-channel must surround glazing cut-out.
 
Multiple glazing with maximum clear view size area shall be 1296 square inches (maximum height and maximum width cannot be combined)
 
LOUVERS
 
Permitted Listed louver for use in 3 hour rated steel fire doors. Maximum dimensions are 24 in wide x 24 in high (576 sq. in)
 
Protection/Kick plate:- Protection plates of size 1219mm wide x 1168 mm height of brass, bronze, steel, stainless steel, cold rolled or aluminum.
 
The top of the plate shall be a maximum of 48 inches above the bottom of the door. Plates may be installed on one or both sides of the door. Maximum plate thickness: 1.5mm.
 
See manufacturer’s installation instructions for additional information on Smoke and Draft Control, size restrictions, and limitations.

The product noted above has been tested and qualified per UL 10C for a 3 Hour Positive Pressure Fire Rating. Also meets the requirements of UL 10B, CAN/ULC S104 and NFPA 252.

The doors noted above are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H individual gasket manufacturer's listings.
Listing Report Certificate of Compliance Return to Search
Attributes
Certificate Date of ExpiryDecember 31, 2026
Certificate Date of Initial RegistrationJanuary 01, 2013
Certificate NumberWHI13 - 20363509
CriteriaCAN / ULC S104 (2015) (R2020)
CriteriaUL 10(c) (2016)
CriteriaUL 10(b) (2008) (R2015)
CriteriaNFPA 252 (2017)
CSI Code08 11 13 Hollow Metal Doors and Frames
Fire Resistance45 Min PP Category A Door
Fire Resistance2 Hour Fire Rated
Fire Resistance1 Hour Fire Rating
Fire Resistance3 Hour Fire Rated
Fire Resistance90 Minute Fire Rated
Label TraceabilityW/N 10094 (45minute rating), W/N 16650 (1hr rating), W/N 10089 (1-1/2 hr rating), W/N 16652 (2hr rating), W/N 10092 (3hr rating); Smoke rated label: W/N 21273-45 Minutes; W/N 21272-60 Minutes; W/N 17040- 90 Minutes; W/N 21271-120 Minutes; W/N 17041:180 Minutes
Listing SectionCATEGORY A - DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Spec ID27736
Design Documents
No Results
Public Documents
No Results