Intertek Directory of Building Products

Gensteel - Fire Doors Company: Gensteel Doors USA, LLC

Hollow Metal Type (16, 18, 20 gauge) (Paper Honeycomb Core), Swinging Flush Design Fire Door for installation singly or in pairs in 3 hour locations.
 
Maximum Size of Openings: 8'0" wide x 8'0" high.

Hollow Metal Type (16 gauge) (Paper Honeycomb Core) (Welded Seams), Swinging Flush Design Fire Door for installation singly or in pairs in 3 hour locations.
 
Maximum Size of Openings: 8'0" wide x 8'0" high.

Hollow Metal Type (18 gauge) (Polystyrene Core), Swinging Flush Design Fire Door for installation in single swing 3 hour locations.
Limitations: Cylindrical Latches with a minimum 1/2" latch throw.
 
Maximum Size of Openings: 3'0" wide x 7'0" high

Hollow Metal Type (18 gauge) (Paper Honeycomb Core) (Steel-Stiffened), Swinging Flush Design Fire Door for installation singly or in pairs in 3 hour locations.
Limitations: Mortise or Cylindrical Latches with a minimum latch throw of 1/2"/Surface Mounted Top and Bottom Flush Bolts.
 
Maximum Size of Openings: Singles - 3'0" wide x 7'0" high
Pairs - 6'0" wide x 7'0" high

Hollow Metal Type (16, 18 gauge) (Steel or Stainless Steel-Faced) (Paper Honeycomb Core) ("L" Series*), Swinging Flush Design Fire Door for installation in single swing 3 hour locations.
Limitations: Unit, Mortise or Cylindrical Latches/Concealed or Surface Mounted Vertical Rod or Rim Type Fire Exit Hardware/Louvers not permitted.
 
Maximum Size of Openings: Singles - 3'6" wide x 7'0" high
Pairs - not allowed

Hollow Metal Type (18, 20, 22, 24 gauge) (Steel-Faced) (Foam-Filled) (Americana Series P*), Swinging Flush Design Fire Door for installation singly or in pairs in 20 minute and 3/4 hour locations.
Limitations: Cylindrical Latches with up to a 5" backset/Viewers/Lights - 1,296 sq.in.
 
Maximum Size of Openings: Singles - 3'0" wide x 7'2" high
Pairs - 6'0" wide x 7'2" high

Hollow Metal Type (18, 20, 22, 24 gauge) (Steel-Faced) (Foam-Filled) (Americana Series P*), Swinging Flush Design Fire Door for installation singly or in pairs in 1-1/2 hour locations.
Limitations: Cylindrical Latches with up to a 5" backset/Mortised or Surface Mounted Vertical Rod or Rim Type Fire Exit Hardware/Viewer (limit door to 1 hour maximum)/Lights - 100 sq.in.
 
Maximum Size of Openings: Singles - 3'0" wide x 7'2" high
Pairs - 6'0" wide x 7'2" high

Hollow Metal Type (24 gauge) (Steel-Faced) (Foam-Filled) (Americana Series R*), Swinging Flush Design Fire Door for installation in single swing 20 minute and 3/4 hour locations.
Limitations: Cylindrical Latches with up to a 5" backset/Viewers/Lights - 1,298 sq.in.
 
Maximum Size of Openings: Singles - 3'0" wide x 6'8" high

Hollow Metal Type (24 gauge) (Steel-Faced) (Foam-Filled) (Americana Series R*), Swinging Flush Design Fire Door for installation in single swing 1-1/2 hour locations.
Limitations: Cylindrical Latches with up to a 5" backset/Viewers (limit door to 1 hour maximum)/Lights - 100 sq.in.
 
Maximum Size of Openings: Singles - 3'0" wide x 6'8" high.

Hollow Metal Type (16, 18 gauge) (Steel or Stainless Steel-Faced) (Paper Honeycomb Core) (L Series*), Swinging Flush Design Fire Door for installation singly or in pairs in 20 minute and 3/4 hour locations.
Limitations: Unit, Mortise or Cylindrical Latches with up to a 5" backset/Mortised or Surface Mounted Vertical Rod or Rim Type Fire Exit Hardware/Viewers/Lights - 1,296 sq.in./Louvers - 24" x 24" (Not Allowed in 20 minute)/Temp. Rise - none.
 
Maximum Size of Openings: Singles - 3'6" wide x 8'0" high or 4'0" wide x 7'2" high
Pairs - 8'0" wide x 7'2" high
Stainless Steel Single Swing - 3'6" wide x 7'0" high

Hollow Metal Type (16, 18 gauge) (Steel or Stainless Steel-Faced) (Paper Honeycomb Core) (L Series*), Swinging Flush Design Fire Door for installation singly or in pairs in 1-1/2 hour locations.
Limitations: Unit, Mortise or Cylindrical Latches with up to a 5" backset/Mortised or Surface Mounted Vertical Rod or Rim Type Fire Exit Hardware/Viewers/Lights - 100 sq.in./Louvers -24" x 24"/Temp. Rise - none.
 
Maximum Size of Openings: Singles - 3'6" wide x 8'0" high or 4'0" wide x 7'2" high
Pairs - 8'0" wide x 7'2" high
Stainless Steel Single Swing - 3'6" wide x 7'0" high

*Manufacturer's Designation
Listing Report Return to Search
Attributes
CriteriaUBC 7-2 (1994)
CriteriaASTM E152-81AE02
CriteriaNFPA 252 (2008)
CriteriaUL 10(b) 2008 (R2009)
CriteriaCAN / ULC S104 (2010)
CSI Code08 11 13 Hollow Metal Doors and Frames
Listing SectionDOORS
Spec ID27807
Design Documents
No Results
Public Documents
No Results