Hollow Metal Type (16, 18 Gauge) Vertically Stiffened, Swinging Flush Design Fire Door for installation Singly or in Pairs, including Double Egress installed in Labeled 14, 16 Gauge Steel Frame in 1/3 hour to 3 hour locations greater than 650°F Temperature @ 30 minutes.
Limitations: Double Egress Pairs up to 1-1/2 hour only. Surface, Concealed Vertical Rod, Rim Fire Exit Hardware, including Top Rod only and Single Point Mortise Fire Exit Hardware. Vision Light Kit - maximum 1296 sq.in. for 20/45 minute; 100 sq.in. for 60/90 minute.
| Configuration: |
Maximum Size: |
Single: Pair: Double Egress: |
4'6" wide x 10'0" high 9'0" wide x 10'0" high 8'0" wide x 10'0" high |
Hollow Metal Type (16, 18 Gauge) (Steel Faced) (Vertically Stiffened) (1-3/8" Thick) Swing Flush Design Fire Door and Transom Panel Combination for installation in 20 minute locations (Without Hose Stream).
Limitations: Cylindrical Latch with Minimum 1/2" Bolt Throw and Maximum 2-3/4" Backset/Viewer. Rabbeted Edge Required between Door and Transom Panel. Must be installed in 16 Gauge or Heavier Steel Door and Transom Frame.
| Configuration: |
Maximum Size: |
Single Door/Transom Combination: Door: Transom: |
2'8" wide x 8'0" high 2'8" wide x 6'8" high 2'8" wide x 1'4" high |
Hollow Metal Type (16, 18 Gauge) (Vertically Stiffened) Swinging Flush Design Fire Door for Installation Singly or in Pairs in 1 hour locations.
Limitations: Unit, Mortise, Cylindrical Latches with up to 5" Backset/Mortised, Surface Mounted Vertical Rod Fire Exit Hardware/Surface Mounted Rim Type Fire Exit Hardware/Mortised, Surface Mounted Manual, Automatic Top and Bottom (Flush) Bolts/Astragals required on Pairs. (Exception: Astragal not required on up to a 1 hour rating with Vertical Rod Fire Exit Hardware one each Door Leaf/Lights - up to 864 sq.in. using Firelite, Firelite Plus Ceramic Glazing using 1/2" High Stops).
| Maximum Size of Openings: |
Singles: 4'0" wide x 10'0" high Pairs: 8'0" wide x 10'0" high |
Hollow Metal Type (16 Gauge) (Vertically Stiffened) Swinging Flush Design Fire Door for Installation Singly or in Pairs (Including Double Egress) in 3 hour locations.
Limitations: Unit, Mortise, Cylindrical Latches with up to a 5" Backset/Mortised, Surface Mounted Vertical Rod Fire Exit Hardware/Surface Mounted Rim Type Fire Exit Hardware/Mortised, Surface Mounted Manual, Automatic Top and Bottom (Flush) Bolts/Astragals required on Pairs. (Exception: up to a 1-1/2 hour rating with Vertical Rod Fire Exit Hardware one each Door Leaf, Astragal is not required).
| Maximum Size of Openings: |
Singles: 4'0" wide x 10'0" high Pairs: 8'0" wide x 10'0" high (including Double Egress) |
Testing Standards: UBC-7-2-97/UL-10C (Positive Pressure).