Mineral Core Type (Wood Faced), Swinging flush design fire door of 90 minute door construction for installation singly or in pairs in 45 minute locations using a field applied edge-sealing system. For use in any "Category C - Standard" frame. Also may be used in any Steel frame listed in "Category C - Proprietary" in accordance with the door manufacturer's installation instructions. Please refer to the door manufacturer's installation instructions for edge-seal system requirements.
Limitations: Cylindrical/Mortise Latches with minimum 1/2" bolt throw and up to 5" Backset/Deadbolts/Surface Mounted Vertical Rod Fire Exit Hardware Mortise/Rim Type Fire Exit Hardware/Automatic/Manual Flush Bolts/Surface Bolts/Vision Panels up to 100 sq.in. using Intumescent Strips/Plates up to 48". 4-Point Latching Required for Pairs. See Manufacturer's installation instructions.
Configuration |
Maximum Size |
Single Swing |
4'0" wide x 9'0" high 4'0" wide x 8'0" high |
Standard Pairs |
8'0" wide x 8'0" high |
*See manufacturer's installation instructions for additional information, restrictions and limitations.
Testing Standards: UBC-7-2-97/UL-10C (Positive Pressure).