Coopers Fire Ltd. SmokeStop Smoke Barrier (With Overlap) protective curtain assembly, for use in steel stud/gypsum or masonry wall applications.
AIR LEAKAGE RATINGS
Test Standard |
Test Type |
Ratinga, b |
UL 1784 |
Ambient Temperature |
≤3.0 cfm/ft2 at up to 0.10 in. of w.c. |
UL 1784 |
Elevated Temperature |
≤3.0 cfm/ft2 at up to 0.10 in. of w.c. |
aThis assembly was tested with an artificial bottom seal. The assembly is not to be installed in areas where pressurization is provided to control smoke movement in accordance with Section 4.3.2 of NFPA 105 (2019) or for hoistway opening protection and lobby doorways where prohibited in Chapter 30 of the 2018 IBC
bA pair of two-inch brushes are required at the head of the curtain to meet air leakage ratings, a single one-inch brush at each side guide is optional based on test results. Brushes must be listed & labeled for fire applications.
SIZE LIMITATIONS
Minimum (Tested) Size |
Maximum Sizea |
7’0” tall x 7’0” wide |
48’0” tall x 500’0” wide |
aOversize labels are not required for this assembly. Assembly dimensions must comply with the minimum and maximum values listed above.
Minimum Bottom Bar weight: 0.30 lbs per sq. ft. of curtain area
Maximum Curtain Rivet spacing: 15” on-center
Side Guide anchorage: 1/4" anchors spaced maximum 18” on-center
Top Hood/Assembly mounting: maximum 40” on-center
Minimum Overlap: 23-5/8" (600mm)
Passage Door (Optional): A passage door using a split bottom bar secured by stainless steel hook & loop may be incorporated into the curtain at overlap locations