Intertek Directory of Building Products

Pawlings 90 Min PVC Impact Protection System PRO-TEKĀ® for Wood or Metal Fire Doors Company: Pawling Corporation

These products are impact protection coverings made of rigid vinyl (PVC) that can be affixed to the surfaces of either single or pairs of metal or wood fire doors, which have been fire rated for 1-1/2 hours. The materials are affixed using contact adhesives or stainless steel screws with cup washers. An extruded or formed PVC compound with maximum dimensions as described in the Tables below:

 

Cladding Sheets (Max. in.)

 

Designation

Thickness

Width

Height

WC-60

0.060

72 (wood) 42 (steel)

108 (wood) 96 (steel)

WC-40

0.040

72 (wood) 42 (steel)

108 (wood) 96 (steel)

WC-28

0.028

72 (wood) 42 (steel)

108 (wood) 96 (steel)

 

 

Kick Plates and Push Plates (Max. in.)

 

Designation

Thickness

Width

Height

KPV-60

0.060

72 (wood) 42 (steel)

108 (wood) 96 (steel)

KPV-40

0.040

72 (wood) 42 (steel)

108 (wood) 96 (steel)

PPV-60

0.060

72 (wood) 42 (steel)

108 (wood) 96 (steel)

PPV-40

0.040

72 (wood) 42 (steel)

108 (wood) 96 (steel)

 

Door Knob Protectors for Wood or Steel Doors (Max. in.)

 

Designation

Thickness

Width

 

Height

DKP-6

0.060

N/A

 

N/A

DKP-12

0.093

N/A

 

N/A

DKP-10

0.093

N/A

 

N/A

 

Door Frame Guards for Wood or Steel Doors (Max. in.)

Designation

Thickness

Width

Height

DFC-1

0.060

Frame Shape

108 (wood)
96 (steel)

DFG-30 Cover

0.093

2 by 2

108 (wood)

96 (steel)

DFG-30 Retainer

0.063

2 by 2

108 (wood)

96 (steel)

DFG-30 Top Cap

N/A

2 by 2

N/A

 

Tests

ASTM E 84

Flame Spread Index          5

Smoke Developed Index    185

 

NFPA 252

Reference Listed Design Section

Design No.

Rating

DFG 100

1-1/2 hour

DFG 102

1-1/2 hour

DFG 103

1-1/2 hour

DFG 104

1-1/2 hour

Listing Report Return to Search
Attributes
CriteriaASTM E84 (2001)
CriteriaNFPA 252 (1999)
CriteriaASTM E84 (2010)
CriteriaASTM E84 (2010b)
CriteriaASTM E84 (2011a)
CriteriaASTM E84 (2012)
CriteriaASTM E84 (2011c)
CriteriaASTM E84 (2011b)
CSI Code08 90 00 Louvers and Vents
CSI Code10 26 00 Wall and Door Protection
Listing SectionBUILDING MATERIALS WITH SURFACE BURNING CHARACTERISTICS
Spec ID28381
Design Documents
Public Documents
No Results