Intertek Directory of Building Products

Smoke Guard® Model 200 Company: Smoke Guard, Inc.

System Description:  The Smoke Guard Model 200 (M200) System creates a code-compliant smoke and draft control assembly when paired with common fire-rated elevator doors.  The Smoke Guard M200 System screen consists of a reinforced, transparent, polyamide or polyimide film.  The film edge is connected to flexible magnetic strips which adhere to ferrous metal rails as the system deploys creating a tight seal.

The Smoke Guard M200 System includes a control system consisting of a printed circuit board containing the control, alarm and diagnostic logic.  The M200 uses standard building power and an optional battery backup system if available to maintain operation during building power failure.
The Smoke Guard Model 200 System is designed for application for a maximum hoistway opening of 70-1/2 inches wide, and a maximum ceiling height of 144 inches.  Additional installation components are required for openings greater than 55-1/4 inches wide.

System Operation:  The Smoke Guard system is designed to protect elevator openings and the shaft from vertical smoke migration. The system will deploy only when the smoke detector in front of that particular elevator opening goes into alarm.

FLAME SPREAD RATINGS
Test Standard Flame Spread Smoke Development
ASTM E84 ≤ 25 ≤ 450
CAN/ULC S102 30 30

AIR LEAKAGE RATINGS
Test Standard Test Type Ratinga
UL 1784 Ambient Temperature ≤3.0 cfm/ft2 at up to 0.30 in. of w.c.
UL 1784 Elevated Temperature ≤3.0 cfm/ft2 at up to 0.30 in. of w.c.
aThis assembly was tested without an artificial bottom seal. The assembly may be installed in areas where pressurization is provided to control smoke movement in accordance with Section 4.3.2 of NFPA 105 (2019) and for hoistway opening protection and lobby doorways as allowed in Chapter 30 of the 2018 IBC.

EGRESS RATING
Test Standard Test Type Rating
ASME A17.1 Section 2.11.6.3, Unrestricted Egress Complies
Listing Report Certificate of Compliance Return to Search
Attributes
Certificate Date of ExpiryDecember 31, 2025
Certificate Date of Initial RegistrationFebruary 1, 2017
Certificate NumberWHI17 - 20797301
CriteriaUL 1784 (2015)
CriteriaASME A17.1 (2.11.6.3) (2013)
CriteriaASTM E84 (2016)
CriteriaCAN / ULC S102 (2018)
CriteriaASTM E84 (2020)
CSI Code07 87 00 Smoke Containment Barriers
Listing SectionBUILDING MATERIALS WITH SURFACE BURNING CHARACTERISTICS
Listing SectionSMOKE CONTROL DOOR ASSEMBLIES
Spec ID28501
Design Documents
No Results
Public Documents
No Results