Rupp Air Management Systems Double Wall Duct Company: Rupp Air Management Systems, Inc.

PRODUCT DESCRIPTION:
  • Double Wall Duct:
    • Insulated, Double-wall, circular cross-section grease duct
    • Inner duct: 20-gauge stainless steel
    • Interstitial Insulation: lightweight wool fibers
    • Outer casing: 24-gauge aluminized carbon steel or stainless steel
    • Maximum Diameter (inner duct): 18-inch for Model RDW-2R; 24-inch nominal for Model RDW-3R; and, 36-inch for Model RDW-3Z
    • Maximum Section Length: 47 inches
 
RATINGS
Standard Rating Design Number
UL 1978 Pass – Zero clearance to combustibles RMS/FMF 120-02
UL 2221 Internal Fire Test, Condition B –
Clearance to Combustibles:
RDW-2R, Up to 16-in. dia., 3/4-in. to duct wall;
RDW-2R, 18-in., 1-in. dia. 1-in. to duct wall;
RDW-3R, Up to 24-in., 3/4-in. to duct wall
Fire-Engulfment Test – 2 h
RMS/FMF 120-01
UL 2221 Internal Fire Test, Condition B – Pass
Clearance to Combustibles: ¾-inch to duct wall;
Internal Fire Test, Condition A - Pass
Fire-Engulfment Test – 2 hr
RMS/FMF 120-02
CAN/ULC S144 Internal Fire Test – Pass
Fire-Engulfment Test – Pass
Fire Resistance Rating - 2 hr
RMS/FMF 120-03
ASTM E814 F-Rating - 2 hr
T-Rating - 2 hr
RMS/FMF 120-01;
RMS/FMF 120-02
CAN/ULC S115 F, FT, FH, FTH-Rating - 2hr RMS/FMF 120-01
RMS/FMF 120-03
UL 1978
CAN/ULC-S662
Clearance to Combustibles:
RDW-2R, Up to 16-in. dia., 3/4-in. to duct wall;
RDW-2R, 18-in., 1-in. dia. 1-in. to duct wall;
RDW-3R, Up to 24-in., 3/4-in. to duct wall
RMS/FMF 120-01
 
 
Listing Report Return to Search
Attributes
CriteriaUL 1978 (2005)
CriteriaUL 2221 (2001)
CriteriaUL 2221 (2010)
CriteriaUL 1978 (2010)
CriteriaCAN / ULC S662 (2009)
CriteriaCAN / ULC S115 (2011)
CriteriaCAN / ULC S144 (2012)
CriteriaUL 1978 (2013)
CriteriaASTM E814-13a (R2017)
CriteriaCAN / ULC S115 (2018) Ed. 5
CSI Code05 58 00 Formed Metal Fabrications
Fire Resistance2 Hour
Listing SectionFIRE RESISTANT DUCT
Spec ID28603